FR200F series Special Purpose Inverter
- 9 -
5
)
Terminal
PE
◆
This terminal must be reliably connected to the main earthing conductor. Otherwise, it may cause
electric shock, mal-function or even damage to the AC drive.
◆
Do not connect the earthing terminal to the neutral conductor of the power supply.
1.4.2 Control circuit terminals
DI1
+24V
DI2
PLC
DI3
COM
DI4
DI5
COM
DI6
Y1
Y2
+10V
R1A R1B R1C
R2A R2B R2C
AO1
AI1
GND
AI2
485+
AI3
485-
PE
DI7/HI
AO2
GND
Figure 1-14
Control circuit terminals diagram
Table 1-4 FR200F
Control circuit terminals functions
Type
Terminal
Marks
Name
Function Description
Power
supply
+10V-GN
D
+
10V power
supply
P10 V power supply to external unit.
Maximum output current: 10 mA
Generally, it provides power supply to external
potentiometer with resistance range of 1–5 kΩ.
+24V-CO
M
24V power supply
P24 V power supply to external unit.
Generally, it provides power supply to DI/DO
terminals and external sensors.
Maximum output current: 200 mA
PLC
Input terminal of
external power
supply
Connect to +24 V by default.
When DI1-DI7 need to be driven by external
signal, PLC needs to be connected to external
power supply and be disconnected from +24 V.
Analog
input
AI1-GND
Analog input 1
Input range: DC 0
~
10V/0
~
20mA, selected by
toggle switches AI1
、
AI2 on control board
Input Impedance: 250 kΩ (voltage input), 250 Ω
(current input)
AI2-GND
Analog input 2
AI3-GND
Analog input 3
Input Voltage Range: DC -10
~
+10V
Input impedance: 250kΩ
Switch
input
DI1- COM
Switch input
terminals 1
Maximum input frequency: 200Hz
Impedance: 2.4kΩ
Voltage range for level input: 9V
~
30V
DI2- COM
Switch input
terminals 2
DI3- COM
Switch input
terminals 3
DI4- COM
Switch input
terminals 4
DI5- COM
Switch input
terminals 5
DI6- COM
Switch input
terminals 6
DI7/HI-CO
M
Switch input
terminals 7 or
high-speed pulse
input
Besides features of DI1–DI6, it can be used for
high-speed pulse input.
Maximum input frequency: 100 kHz
Analog
Output
AO1-GND
Analog Output 1
Output range: DC 0
~
10V/0
~
20mA, selected by
toggle switches AO1
、
AO2 on control board
Impedance requirements≥10kΩ
AO2-GND
Analog Output 2