FR200F series Special Purpose Inverter
- 20 -
31: Run command switched to
communication control
32: Count input
33: Count clear
34: Length count
35: Length clear
36: DC brake input command at
Stop
37: Speed/torque control switch
38
~
99:reserved
F04.10
Filtering time of digital
input terminal
0.000
~
1.000s
0.010s
△
F04.11
Delay time before terminal
DI1 is valid
0.0
~
300.0s
0.0s
△
F04.12
Delay time before terminal
DI2 is valid
0.0
~
300.0s
0.0s
△
F04.13
Terminal DI1
~
DI5
positive/negative logic
DI5
、
DI4
、
DI3
、
DI2
、
DI1
00000
×
0: Positive logic(Terminals are on
at 0V/off at 24V)
1: Negative Logic (Terminals are
off at 0V/on at 24V)
F04.14
Terminal DI6
~
AI3
positive/negative logic
AI3
、
AI2
、
AI1
、
DI7
、
DI6
00000
×
0: Positive logic
1: Negative Logic
F04.15
FWD/REV terminal
control mode
0: Two-wire mode 1
0
×
1: Two-wire mode 2
2: Three-wire mode 1
3: Three-wire mode 2
F04.16
Terminal UP/DOWN
frequency adjustment
control
Unit's place: action when stop
001
×
0: Clear
1: Holding
Ten’s place: action on power loss
0: Clear
1: Holding
Hundreds place: integral function
0: No integral function
1: Integral function enabled
F04.17
Terminal UP/DOWN
frequency change step
size
0.00
~
50.00Hz 0.00:Disabled
1.00Hz/
200ms
△
F04.18
Terminal action selection
when power on
0:Level effective
0
×
1:Edge tLevel effective
F04.19
Delay time before terminal
DI1 is invalid
0.0
~
300.0s
0.0s
△
F04.20
Delay time before terminal
DI2 is invalid
0.0
~
300.0s
0.0s
△
Group F05 Digital Output
F05.00
Y1 output function
0: No output
1: Drive is running
2: Fault output
3: Frequency-level detection FDT1
output
4: Frequency-level detection FDT2
output
5: Drive in 0Hz running 1(no output
at stop)
1
×
F05.01
Y2 output function
3
F05.02
Relay 1 output function
2
×
F05.03
Relay 2 output function
11
×