![Frecon FR200F Series User Manual Download Page 25](http://html1.mh-extra.com/html/frecon/fr200f-series/fr200f-series_user-manual_2329261025.webp)
FR200F series Special Purpose Inverter
- 25 -
boost
F09.03
Multi-point V/F frequency
1(F1)
0.00
~
F09.05
0.00Hz
△
F09.04
Multi-point V/F voltage 1
(V1)
0.0
~
100.0
0.0%
△
F09.05
Multi-point V/F frequency
2(F2)
F09.03
~
F09.05
0.00Hz
△
F09.06
Multi-point V/F voltage 2
(V2)
0.0
~
100.0
0.0%
△
F09.07
Multi-point V/F frequency
3(F3)
F09.05
~
F09.09
0.00Hz
△
F09.08
Multi-point V/F voltage 3
(V3)
0.0
~
100.0
0.0%
△
F09.09
Multi-point V/F frequency
4(F4)
F09.07
~
rated motor frequency
50.00Hz
△
F09.10
Multi-point V/F voltage 4
(V4)
0.0
~
100.0 Ue=100.0%
100.0%
△
F09.11
V/F slip compensation
gain
0.0
~
300.0%
0.0%
△
F09.12
Stator voltagedrop
compensation gain
0.0
~
200.0%
100.0%
△
F09.13
Excitation boost gain
0.0
~
200.0%
100.0%
△
F09.14
Oscillation Suppression
0.0
~
300.0%
Model
defined
△
F09.15
Voltage source for V/F
separation
0: Digital setting (F09.16)
0
×
1:keypad potentiometer
2:AI1
3: Multi-reference
4: Pulse setting ( DI7/HI )
5: PID
6:AI2
7:AI3
F09.16
Voltage digital setting for
V/F separation
0 V to rated motor voltage
0.0%
△
F09.17
Voltage rise time of V/F
separation
0.0
~
6000.0s
It indicates the time for the
voltage rising from 0 V to rated
Motor voltage.
0.1s
△
Group F10 Vector Control Parameters of Motor 1
F10.00
Speed/torque control
0: speed control
0
×
1: torque control
F10.01
ASR low-speed
proportional gain Kp1
0.0
~
100.0
30.0
△
F10.02
ASR low-speed
integration time Ti1
0.01
~
10.00s
0.50s
△
F10.03
ASR switching
frequency 1
0.00
~
F10.06
5.00Hz
△
F10.04
ASR high-speed
proportional gain Kp2
1
~
100.0
10.0
△
F10.05
ASR high-speed
integration time Ti2
0.01
~
10.00s
0.100s
△
F10.06
ASR switching
frequency 2
F10.03
~
Fmax
10.00Hz
△
F10.07
ASR input filtering time
0.0
~
500.0ms
0.3ms
△
F10.08
ASR output filtering time
0.0
~
500.0ms
0.0ms
△
F10.09
Vector control slip gain
50
~
200%
100%
△