FR150A Series Multifunctional Compact
Inverter
- 35 -
run
3: Fault protection disabled
Ten's place: Power input phase
Loss (Err09)(Same as unit's
place )
Hundred's place: Power output
phase loss(Err10)(Same as unit's
place )
Thousand's place: Motor overload
(Err11)(Same as unit's place )
Ten thousand's place: Inverter
overload(Err11)(Same as unit's
place )
F11.11
Protection action 2
External equipment fault
(
Err13)
0: Fault reported and coast to
stop
1: Stop according to the stop
mode
2: Fault reported but continue to
run
00000
×
Ten's place: EEPROM read/write
fault (Err15) (Same as unit's place)
Hundred's place: Communication
overtime error (Err18) (Same as
unit's place)
Thousand's place: PID feedback
loss (Err19) (Same as unit's place)
Ten thousand's place: Continuous
running time reached (Err20)
(Same as unit's place)
F11.12
Protection action 3
Unit's place: Module temperature
detection disconnection
(
Err24)
0: Fault reported and coast to
stop
1: Stop according to the stop
mode
2: Fault reported but continue to
run
00030
×
Ten's place: Load becoming 0
(Err25) (Same as unit's place)
F11.14
Frequency selection for
continuing to run upon
fault
0: Current running frequency
1
×
1: Set frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
Abnormality
F11.15
Backup frequency upon
abnormality
0.00
~
Fmax
0.00Hz
×
F11.17
Motor overload protection
time
30.0
~
300.0s
60.0s
×
F11.18
Overload alarm
Unit's place: detection option:
0: Always detect
1: Detect at constant speed only
00000
×