![Frecon FR150A Series Manual Download Page 14](http://html1.mh-extra.com/html/frecon/fr150a-series/fr150a-series_manual_2329259014.webp)
FR150A Series Multifunctional Compact
Inverter
- 14 -
2.1.2
Control circuit terminals
◆
Control circuit terminals(<5.5kW):
DI1
+24V
DI2
DI3
DI4
+10V
R1A R1B R1C
AI1
AI2
485+
AO1
GND
DI7/HI
Y1
GND
485-
PLC
Fig.2-5 Control circuit terminals (<5.5kW)
Table 2-2 FR150A
Description of control circuit terminals
Type
Terminal
Name
Function Description
Power supply
+10V-GND
Ex10 V
power supply
P10 V power supply to
external unit.
Generally, it provides power supply to
external potentiometer with resistance
range of 1
–5 kΩ.
Maximum output current: 10 mA
+24V-GND
Ex24V
power
supply Applying
to Overvoltage
Category II
circuit
P24 V power supply to
external unit.
Generally, it provides power supply to
DI/Do terminals and external sensors.
Maximum output current: 200 mA
PLC
Input terminal
of
external power
supply
Connect to +24 V by default.
When DI1-DI7 need to be driven by
external signal, PLC needs to be
connected to external power supply
and be disconnected from +24 V.
Analog input
AI1-GND
Analog input 1
Input voltage range: DC 0
~
10V/0
~
20mA
,
decided by toggle switches
AI1
、
AI2 on the control board
Impedance: 250 kΩ (voltage input),
250 Ω (current input)
AI2-GND
Analog input 2
Switch input
DI1- GND
Switch input
terminals 1
Maximum input frequency:200Hz
Impedance:
2.4kΩ
Voltage range for level input:9V
~
30V
DI2- GND
Switch input
terminals 2
DI3- GND
Switch input
terminals 3
DI4- GND
Switch input
terminals 4
DI7/HI-GND
Switch input
terminals 7 OR
High-speed
pulse input
Besides features of DI1
–DI4, it can be
used for high-speed pulse input.
Maximum input frequency: 100 kHz
Analog
output
AO1-GND
Analog output
terminal 1
Output voltage range:0
~
10V
Impedance requirements≥10kΩ
Switch output
Y1-GND
Open collector
output 1
Voltage range:0
~
24V
Current range:0
~
50mA
Relay output
R1A-R1C
Normally open
Contact driving capacity: