FR150A Series Multifunctional Compact
Inverter
- 36 -
Ten's place : compared object
0: Rated current of motor
1: Rated current of drive
Hundred's place: report fault or not
0: Not report fault
1: Report fault
2:Show warning
Thousand's place: deceleration or
not
0: Deceleration
1: Not deceleration
Ten thousand's place: given mode
for overload threshold
0: F11.19 set
1: F11.19*VP
2: F11.19*AI1
3: F11.19*AI2
4: F11.19*AI3
F11.19
Overload alarm threshold
0.0
~
200.0%
130.0%
×
F11.20
Overload alarm
activated time that
exceeding threshold
0.1
~
60.0s
5.0s
×
F11.21
Inverter overheat warning
threshold
50.0
℃~
over heat temperature
Base on
model
×
F11.22
Detection level of power
loss
5.0
~
100.0%
20.0%
×
F11.23
Detection time of power
loss
0.1
~
60.0s
5.0s
×
F11.24
Action selection at
instantaneous power
failure
0: Disabled
1
×
1: Deceleration
2: Bus voltage constant control
F11.25
Decel time at
instantaneous power
failure
0.0
~
6000.0s
5.0s
△
F11.26
Rapid current limit
0: Disabled
0
×
1: Enabled
F11.27
Times of automatic
reset
0
~
20
0
×
F11.28
Interval of automatic
reset
0.1
~
100.0s
1.0s
×
F11.29
DO action during fault auto
reset
0: Not act
0
×
1: Act
F11.30
Instantaneous power off
bus voltage
60.0%
~
Recovery voltage
80.0%
△
F11.31
Instantaneous power off
recovery voltage
Power off voltage
~
100.0%
85.0%
△
F11.32
Instantaneous power off
voltage judge time
0.01
~
10.00s
0.10s
△
F11.33
Instantaneous power off
gain Kp
0.1
~
100.0%
40.0%
△
F11.34
Instantaneous integration
time Ti
0.00
~
10.00s
(
0.00:Integration
invalid
)
0.10s
△
Group F12: Multi-Reference and Simple PLC Function
F12.00
Reference 0
-100.0
~
100.0%
0.0%
△