background image

1.

2.

3.

How to navigate this chart:

Identify symptom @ top left

Move to right and find highlighted cells that 

identify possible causes below

Move down below listed causes and find 

highlighted cells that identify remedies to the 

bottom left

CAUSES

Breaker tripped, open switch or loose wire connctions

Improper electrical connections

Defective motor

Improper voltage connection

Poor motor ventilation

Improper running voltage at motor terminals

Pump is not primed

Plumbing suction leak

Plumbing discharge leak

Discharge or suction piping plugged, valve closed

W

ater level is more than 25 feet below injector (This applies to a 

deep well application with a 25 foot tail pipe) 

W

ater level below injector is deeper than anticipated

Injector nozzle plugged

Impeller ports plugged

Leaking check or foot valve

W

ater logged pressure tank

High friction loss between pump and pressure tank, partially  closed discharge valve

Pressure switch cut-out setting too high

Suction line restriction, suction piping too small, partially closed  suction valve

Deep well control valve open too much

W

ater level drops below suction inlet

Recharge pressure tank to 2 PSI below pressure 

switch cut-in setting

Increase size or clean out discharge pipe between 

pump and pressure tank

Lower pressure switch cut-out pressure as described 

in"PRESSURE SWICH ADJUSTMENT" in this manual

Increase size or clean out suction piping to pump

Clear nozzle or impeller of clogging debris. See 

"PUMP DISASSEMBLY" in manual
Convert a shallow well application into a deep well 

arrangement. Lower the injector setting in a deep well 

application
Consult pump performance table and select alternate 

injector assembly or pump that will produce required 

performance at well conditions

Replace faulty check or foot valve

Make sure motor vents are not blocked and/or 

improve vent clearance around motor

Follow "PRIMING THE PUMP" proceedure as outlined

in this manual

Check all plumbing joints and connections for leaks

Make sure all valves are fully open and all piping is 

free from obstructions

Have qualified elctrician check for low or high running 

voltage at motor terminal.  Electrician will need to 

correct if necessary.

Excessive air in water

Check wiring, switches and breakers

Call your dealer

Make sure motor voltage setting and incoming voltage

match

Excessive cycling of pump

Loss of pressure with no water usage

Pump runs continuously

Gravelly noise from pump

SYMPT

OMS

CVJ TROUBLESHOOTING GUIDE

REMEDIES

Perform "CONTROL VALVE ADJUSTMENT" as 

described in this manual
For shallow well applications lower suction inlet in 

well.  If this length becomes greater than 25 feet, you 

will need to convert to a deep well system. For deep 

well applications you will need to lower the injector in 

the well.

Motor not running

Motor overheats

Pump does not deliver water or pressure

Low pressure from pump

Low flow from pump

Summary of Contents for VersaJet Series

Page 1: ...otor or tank WARNING Hazardous voltage Can shock burn or cause death Ground pump before connecting to power supply Disconnect power before working on pump motor or tank WARNING CAUTION CAUTION WARNING...

Page 2: ...to make sure there is no damage or broken parts that may have occurred in shipping If damage is evident report this immediately to your shipping carrier and dealer The shipping carrier assumes full r...

Page 3: ...y have to be increased in diameter to reduce pressure loss The pressure loss in a system increases 1 As the flow rate increases 2 As the piping size decreases Consult included friction loss tables App...

Page 4: ...pumping of a low yield well Lower the injector assembly into the well It should be set at least 3 below the lowest dynamic water level if you are not using a tail pipe below the injector The foot val...

Page 5: ...e that has an alternate NPT pressure switch connection This alternate pressure switch connection allows the switch to read the pressure on the outbound side of the valve rather than inside the pump ca...

Page 6: ...mply with National Electric Code NEC or Canadian Electric Code CEC and all applicable local codes All dual voltage units come factory preset for 230 volts Figure 6 Disconnect power at electrical panel...

Page 7: ...filling the pump case completely full of water as damage may occur to the seal and other internal components if run dry PRESSURE SWITCH ADJUSTMENT EXAMPLE ASSUMES PRESSURE SWITCH IS INITIALLY SET WITH...

Page 8: ...g bolted to front of the pump If you need to service the impeller motor or seal use the following procedure going as far as needed to correct the problem 1 Disconnect the power to the unit 2 Disconnec...

Page 9: ...NT in this manual Increase size or clean out suction piping to pump Clear nozzle or impeller of clogging debris See PUMP DISASSEMBLY in manual Convert a shallow well application into a deep well arran...

Page 10: ...4 305374907 305374905 2 Studs B 305465901 3 Bracket 4 O Ring F 305465902 5 Fasteners C 305465903 6 Pressure Switch D 305465904 7 Pressure Hose Fitting 8 Pressure Hose Tubing 9 Plugs E 305465905 10 Mec...

Page 11: ...applicable codes ordinances and good trade practices 3 Product was not installed by a Franklin Certified Contractor or Franklin Key Dealer or 4 Product was damaged as a result of negligence abuse acc...

Page 12: ...106580101 Rev 2 07 13 9255 Coverdale Road Fort Wayne IN 46809 Tel 260 824 2900 Fax 260 824 2909 www franklinwater com...

Reviews: