VCC-20-P CONDENSATE PUMP 

for Plenum Applications

Owner's Manual

The VCC-20-P pump

 is designed to be used in plenum applications and

 is compliant with UL standard 

UL2043, “Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed 
in Air-handling Spaces.” 

This condensate pump automatically removes condensate water that drips from an air 
conditioner evaporator coil, refrigeration equipment coil, condensing furnace, or con

-

densing boiler. The pump is controlled by a float switch mechanism, which automatically 
starts and stops the pump. 
The pump also includes an auxiliary high-water level switch. This switch is configured to 
open a thermostat circuit in the event of high water level in the pump reservoir, thereby 
stopping production of condensate. Alternatively, this switch can be reconfigured by the 
installer to close a circuit in the event of high water level, which operates an external alarm 
or relay, (purchased separately).
Please examine your item(s) carefully to ensure that no damage occurred during shipment. If damage has 
occurred, please contact the place of purchase. They will assist you in replacement or repair, if required.
This product is covered by a Limited Warranty for a period of 12 months from the date of original purchase by the 
consumer. For complete warranty information, refer to 

www.LittleGiant.com

.

Specifications

Model 

Volts

HZ

Amps

Watts

Shut Off

VCC-20-P

115

60

1.5

75

20’ (6.1 m)

VCC-20-P

230

50/60

0.6/0.5

58/60

17’ (5.2 m)

SAFETY INSTRUCTIONS

Before Getting Started

This equipment should be installed and serviced by technically 
qualified personnel who are familiar with the correct selection 
and use of appropriate tools, equipment, and procedures. Failure 
to comply with national and local electrical and plumbing codes 
and within Little Giant recommendations may result in electrical 
shock or fire hazard, unsatisfactory performance, or equipment 
failure.
Know the product’s application, limitations, and potential haz

-

ards. Read and follow instructions carefully to avoid injury and 
property damage. Do not disassemble or repair unit unless 
described in this manual.
Refer to product data plate(s) for additional precautions, operat

-

ing instructions and specifications.
Failure to follow installation or operation procedures and all 
applicable codes may result in the following hazards:

Risk of death, personal injury, or 

property damage due to explosion, fire, 

or electric shock.

Do not use to pump flammable or explosive fluids such as 
gasoline, fuel oil, kerosene, etc.

Do not use in explosive atmospheres or hazardous loca

-

tions as classified by the NEC, ANSI/NFPA70.

Do not handle a pump or pump motor with wet hands or 
when standing on a wet or damp surface, or in water.

When a pump is in its application, do not touch the motor, 
pipes, or water until the unit is unplugged or electrically 
disconnected.

If the power disconnect is out of sight, lock it in the open 
position and tag it to prevent unexpected application of 
power.

If the disconnect panel is not accessible, contact the elec

-

tric company to stop service.

Summary of Contents for Little Giant VCC-20-P

Page 1: ...75 20 6 1 m VCC 20 P 230 50 60 0 6 0 5 58 60 17 5 2 m SAFETY INSTRUCTIONS Before Getting Started This equipment should be installed and serviced by technically qualified personnel who are familiar wi...

Page 2: ...cord The pump should only be used with liquids compatible with pump component materials If the pump is used with liquids incompatible with the pump components theliquid can cause failure to the electr...

Page 3: ...high point slope discharge line down slightly to a point above the drain area Then turn down and route to a suitable drain at a point below or approximately level with the bottom of the pump if possi...

Page 4: ...al forexpected switch operationand wiring connections Connect the switch leads 7 in series with the low voltage thermostat circuit as specified in the heating cooling unit s operating manual 2 The ins...

Page 5: ...down when float is raised If wired to NC terminal external component alarm or relay should activate when float is raised 6 Disconnect the pump from the power source 7 Replace the tank cover assembly...

Page 6: ...rate correctly Check valve stuck or plugged Remove check valve and inspect for proper operation Outlet flow is blocked Check outlet tubing to ensure that it is not kinked or blocked Clear blocked tubi...

Page 7: ...os Vatios Apagado VCC 20 P 115 60 1 5 75 20 6 1 m VCC 20 P 230 50 60 0 6 0 5 58 60 17 5 2 m INSTRUCCIONES SOBRE SEGURIDAD Antes de empezar La instalaci n y el mantenimiento de este equipo deben estar...

Page 8: ...No use un prolongador La bomba solo se debe utilizar con l quidos compatibles con los materiales que componen la bomba Si la bomba se utiliza con l quidos incompatibles con los componentes de la bomb...

Page 9: ...como sea necesario No extienda m s alto que un 75 la capacidad de la carga gal h de la bomba 5 Desde el punto alto baje la l nea de descarga ligeramente hasta un punto encima del rea del drenaje Lueg...

Page 10: ...cables del interruptor 7 en serie con el circuito del termostato de vol taje bajo seg n se especifica en la manual operativo de unidad de calefacci n refrigeraci n 2 El instalador puede reconfigurar...

Page 11: ...aire debe apagarse cuando se eleva el flotador Si est cableado al terminal NC el componente externo alarma o rel debe activarse cuando se eleva el flotador 6 Desconecte la bomba de la fuente de alime...

Page 12: ...est bloqueado Verifique la tuber a de salida para asegurarse de que no est retorcida ni bloqueada Despeje la tuber a bloqueada de lodo y residuos Limpie la tuber a de entrada y de salida El impulsor d...

Page 13: ...6 0 5 58 60 17 5 2 m CONSIGNES DE S CURIT Avant de commencer Cet quipement doit tre install et entretenu par des techniciens qualifi s capables de choisir et d utiliser les outils les quipements et l...

Page 14: ...osants Si la pompe est utilis e avec des liquides incompatibles avec les composants de la pompe le liquide peut provoquer une d faillance du syst me d isolation lectrique entra nant un choc lectrique...

Page 15: ...Ne pas d passer 75 de la charge hydraulique gal h de la pompe 5 partir du point le plus haut inclinez l g rement le tuyau de refoulement vers le bas jusqu un point au dessus de la zone d coulement En...

Page 16: ...n comme indiqu dans le manuel de l unit de chauffage refroidissement 2 L installateur peut reconfigurer cet interrupteur la borne NF pour fermer un circuit basse tension en cas de niveau d eau lev afi...

Page 17: ...enir niveau 3 Mettre la pompe sous tension 4 Tester l interrupteur de fonctionnement de la pompe en faisant mon ter le flotteur Le moteur devrait d marrer avant que le flotteur de l interrupteur ne to...

Page 18: ...assurer que le conden sat r siduel ne cr e pas de poches d acide localis es qui pourraient causer des piq res 6 V rifier les tuyaux d aspiration et de refoulement Nettoyer au besoin V rifier l absenc...

Page 19: ...lle n est pas cou d e ou obstru e Nettoyez la boue et les d bris de tout tuyau obstru Net toyez la tuyauterie d entr e et de sortie La roue de la pompe ne tourne pas Nettoyez toute obstruction dans le...

Page 20: ...ic Co Inc Oklahoma City OK 73157 2010 800 701 7894 littlegiant com Pour l aide technique entrez s il vous pla t en contact Form 998922 R v 003 06 19 Droits d auteur 2019 Franklin Electric Co Inc Tous...

Reviews: