Franklin Electric Co., Inc.
| Oklahoma City, OK 73157-2010
800.701.7894
|
littlegiant.com
For technical assistance, please contact:
Form 998922 Rev. 003 06/19
Copyright © 2019, Franklin Electric, Co., Inc. All rights reserved.
Troubleshooting
Problem
Probable Causes
Corrective Action
Pump does not start when
tank is full of condensate
water.
Pump is not connected to electrical power. Connect pump to a dedicated GFCI circuit.
Circuit breaker off or fuse removed.
Turn on circuit breaker or replace fuse.
Accumulation of debris or build-up on float. Clean float; a dirty float could be too heavy to operate correctly.
Float movement obstruction.
Remove the tank. Check float movement path. Remove any debris or
obstruction.
Defective switch.
Replace pump.
Defective motor.
Replace pump.
Condensate is overflowing
from the tank.
Pump is not connected to electrical power. Connect pump to a dedicated GFCI circuit.
Liquid inflow matches or exceeds pump
output capacity.
Larger pump required.
The high level switch should shut off the A/C unit or signal an alarm in
this condition if connected in the circuit correctly. Check to ensure that
the pump high level switch is connected to the A/C unit (or alarm cir
-
cuit), and that the leads are connected to the correct switch terminals
for the application.
Pump is not level.
Check to ensure that the pump is level. If the pump is not level, it may
not activate, causing water to overflow from the tank. Place unit on a
flat and level surface.
Accumulation of debris or build-up on float. Clean float. A dirty float could be too heavy to operate correctly.
Check valve stuck or plugged
Remove check valve and inspect for proper operation.
Outlet flow is blocked.
Check outlet tubing to ensure that it is not kinked or blocked. Clear
blocked tubing of slime and debris. Clean inlet and outlet piping.
Pump impeller is not turning.
Clear any blockage in the impeller housing.
Defective switch.
Replace pump.
Defective motor.
Replace pump.
Pump will not shut off.
Float movement obstruction.
Remove the tank. Check float movement path. Remove any debris or
obstruction.
Liquid inflow matches or exceeds pump
output capacity.
Larger pump required.
The high level switch should shut off the A/C unit or signal an alarm in
this condition if connected in the circuit correctly. Check to ensure that
the pump high level switch is connected to the A/C unit (or alarm cir
-
cuit), and that the leads are connected to the correct switch terminals
for the application.
Defective switch.
Replace pump.
Pump runs but does not
discharge liquid.
Check valve stuck or plugged.
Remove check valve and inspect for proper operation.
Lift too high for pump.
Check rated pump performance.
Inlet to impeller plugged.
Pull pump and clean.
Outlet flow is obstructed.
Check outlet tubing to ensure that it is not kinked or blocked. Clear
blocked tubing of slime and debris. Clean inlet and outlet piping.
Pump does not deliver
rated capacity.
Check valve stuck or plugged.
Remove check valve and inspect for proper operation.
Lift too high for pump.
Check rated pump performance.
Low voltage, speed too slow.
Check that supply voltage matches nameplate rating.
Impeller or discharge pipe is clogged.
Pull pump and clean. Check pipe for scale or corrosion.
Pump cycles continually.
Check valve leaking.
Remove check valve and inspect for proper operation.