Code
Parameter description
Default
Min
Max
UM
Menu
Note
PH10
Automatic season change-over on fresh air temperature differential
1.0
-20.0
20.0
°C
IS-V
Only if PH09 =5
PH15
Minimum setpoint value
15.0
PH01
PH16
°C
IS-V
PH16
Maximum setpoint value
40.0
PH15
PH02
°C
IS-V
PH18
Delete alarm history
No (0)
No (0)
Yes (1)
-
IS-V
Set YES (1) and wait until the value NO (0)
is displayed again
PH20
Activates the buzzer
Yes (1)
No (0)
Yes (1)
-
IS-V
PH30
Unit of temperature measurement:
0: °Celsius
1: °Fahrenheit
0 (°C)
0 (°C)
1 (°F)
-
IS-V
PH90
User interface language
0: English
1: Italian
2
0
3
-
IS-V
PH99
Restores factory settings by default
No (0)
No (0)
Yes (1)
-
IS-D
Wait until the value NO (0) is displayed
again at the end of the recovery
PSd3
Installer level password (3)
1616
-999
9999
-
IS