5.2.3
MODBUS COMMUNICATION
The MODBUS RTU network must be connected to the MODBUS socket on the PCB.
J3 socket type: PHOENIX CONTACT-MC 1.5/3-ST-3.5 SOCKET, FREE, 3.5 MM, 3 WAY) - France AIR code: 125457.
To use the unit with the ModBus protocol, refer to the specific manual (MODBUS RTU – RS 485 communication
protocol).
5.2.4
GENERAL ALARM RELAY
It is possible to manage a configurable alarm relay. For each type of alarm, a parameter allows you to select
whether the alarm data should be signalled on the alarm relay. Several alarms can be addressed to the
relay.
6
INITIAL SYSTEM START-UP
READ CAREFULLY!
•
Secure the unit. Close it and establish the air connections
•
Connect the power supply (following the diagram on the cabinet)
•
Connect the remote control to the terminal block
•
Do not forget to install the machine protections
•
Check the earthing
•
Check the voltages (240 or 400 V)
•
Close the proximity switch
•
The control unit indicates "checking" and then the screen displays OFF
•
The Power Box® Ready is set to OFF
•
Press ESC to view the alarms and acknowledge them
o
RTC, re-enter the time and date or use the installer/clock menu
o
Start the machine when all faults are eliminated by pressing on ESC
o
Re-enter your parameters, speed, mode and other functions in the installer menu (code 1616)
When the machine is started for the first time: it is necessary to configure the control. Please note that,
by default, the fans are off (corresponding to speed 0)
NB
•
Any intervention on or modification of the unit's internal connection is prohibited and shall
render the warranty void.
•
We recommend using the accessories supplied by us. Please contact France Air in case of doubt
regarding the possibility of using non-genuine accessories.
120 Ω terminal resistor
MODBUS network
GND
-
+