Hampton® H15U-NG/LP Direct Vent Freestanding Gas Stove
23
installation
Offset to Vertical Terminations
Venting Arrangements - Horizontal Terminations
The two diagrams show all allowable combinations of straight horizontal termination with one 45
o
elbow off the unit. Restrictor position "A".
Venting Arrangements
Vertical Terminations Systems for Residential Manufactured and
Mobile Homes
The shaded area in the diagram below shows all allowable combinations of straight
vertical and offset to vertical runs with vertical terminations.
Maximum two 45
o
elbows
.
If the vent is ENCLOSED in a chase (min. size 9" x 9") maintain a 1-1/4" clearance to
combustibles.
May be installed in Manufactured (Mobile) Homes after first sale.
Horizontal Terminations for All Venting
Systems
The shaded areas in the diagram below show all
allowable combinations of vertical runs with hori-
zontal terminations. Maximum one 90
O
elbow (two
45
o
elbows equal one 90
o
elbow).
Propane and Natural Gas: Residential,
Manufactured and Mobile Home Instal-
lations
May be installed in Manufactured (Mobile)
Homes after first sale.
12" max. w/AstroCap or Simpson Duravent Hori-
zontal Square Termination Cap.
24" max. w/FPI Riser or Snorkel Termination Cap.