Ventilated Chase Pan
BEFORE YOU START
Check your inventory list to be sure you have all the necessary parts supplied in good usable
condition. Check for any concealed damage. Check the operation of the combustion air damper.
When the damper is in the fully closed position, the damper handle should be to the left. When
damper is in the fully open position, the damper handle must be in the right position.
INSTALLATION COMPONENTS DIAGRAM
Installation Components
Note: Insulation does not come in contact
with Chimney. Maintain a 2" (51mm)
clearance.
INSTALLATION
CHIMNEY SYSTEM
CONSIDERATIONS
Regency’s FP90 Fireplace is to be installed
with one of the following Chimney Systems
only. Chimney systems only 7" (178mm) or 8"
(203mm) diameter are to be used.
In Canada
Any of the following ULCS 629 listed chimney
systems may be used:
1)
CF Sentinal
2)
SuperPro 2100+
3)
SuperVent 2100+
4)
Security S-2100+
5)
Oliver Macleod
6)
Dura Plus HTC
7)
ICC Excel 2100
Note: 8" (203mm) - 7" (178mm) adapter is
mandatory for installation using 7" (178mm)
chimney. Anchor plate must be purchased
with selected chimney system from Chimney
Supplier.
The use of only one of these systems is permitted
when installing the fi replace. Do not alter or mix
parts from other systems as this may cause a
potential hazard and void Regency’s limited
warranty.
Chimney Height
The total height of your chimney system from the
top of the fi replace to the chimney cap must not
exceed 40'(12m), and must also meet minimum
system height requirements. Please refer to
the fl ue manufacturer's instructions for specifi c
details. Refer to Minimum Recommended Flue
Height section.
Chase Enclosure
A chase is a vertical box-like structure
constructed to surround the fi replace and
chimney. A ventilated chase cap is highly
recommended. Refer to fl ue manufacturer's
instructions for reduced fl ue heights above chase
terminations. As with all chimney installations,
avoid overhead obstructions such as trees,
power lines, etc.
A chase should be constructed just like any out-
side wall, insulated and vapor barriered. Please
check with local building authorities. In a cold
climate, we recommend the base of the chase
be insulated between the solid continuous fl oor
beneath the fi replace and the chase bottom. If
used, the value and amount of chase insulation
in a cold climate installation is optional and not
required for safety. Insulation is recommended
to avoid heat loss.
Inside
Wall
Rain Cap
Storm Collar
Roof Flashing
Attic Radiation
Shield
Nailing Strip
Outside Fresh
Air Duct
Hearth
Extension
Hearth Safety
Strip
Outside Air
Inlet
Framing