FPI FP90 Wood Fireplace
12
INST
ALLA
TION
INSTALLATION MEASUREMENTS / FRAMING DETAILS
INSTALLATION
3" (76mm)
STAND-OFF
2x4 FRAMING
FRONT OF UNIT ONLY
COMBUSTION AIR
TO OUTSIDE
38"
(965mm)
19"
(483mm)
30"
(762mm)
60" (1524mm) WIDE INSIDE MIN.
UNIT TO BE CENTERE
NOTE:
FRAMING TO BE AGAI
STAND-OFFS ONLY
11"
(279mm)
D
NST
24"
(610mm)
VENT TO OUTSIDE
COMBUSTION AIR
11"
(280mm)
HEARTH MUST HAVE 1/2" (127mm)
MILLBOARD UNDER FINISH MATERIAL
WITH MIN. "K" FACTOR OF 20.07
50 3/4"
(1289mm)
44"
(1118mm)
40"
(1016mm)
18"
(457mm)
46"(1168mm)
MIN.
11"
(280mm)
18"
(457mm)
2X4,
2X6,
2X8
ON
END
60"(1524mm)
WIDE INSIDE CHASE MIN.
10"
(254mm)
84" (2134mm)
CEILING
NOTES:
1) CHASE MUST BE 60" (1524mm) WIDE INSIDE AND UNIT TO BE CENTERED IN OPENING.
2) MANTEL MIN. HEIGHT OF 18" (457mm) FROM TOP OF LOUVER OPENING TO UNDERNEATH MANTEL or 55 1/2" (1410mm) FROM BOTTOM OF UNIT.
3) MUST HAVE NON-COMBUSTIBLE MATERIAL EXTENDING 11" (280mm) ON EITHER SIDE AND 9" (229mm) ON TOP. 3/8" (10mm) THICK FINISHING
MATERIAL TO BE INSTALLED ON TOP OF THIS.
4) FRAMING IS SLIGHTLY LARGER THAN UNIT DIMENSIONS TO ALLOW FOR EASIER INSTALLATION (50 3/4", 1289mm H x 44", 1118mm W)
5) MUST MAINTAIN A MIN. OF 46" (1168mm) FROM TOP OF LOUVER OPENING TO FINISHED CEILING.
6) MUST MAINTAIN A MIN. OF 24" (610mm) TO SIDE WALL FROM THE EDGE OF THE TOP LOUVER OPENING.
7) HEARTH MUST BE A MIN. OF 40" (1016mm) WIDE x 18" (457mm) deep and 1/2" (127MM) THICK.
2x4
2x4