background image

Parameter 2:

 Sets the low voltage point in ECO mode. This setting ranges 

from 5% to 10% of the nominal voltage.

Parameter 3: 

Sets the high voltage point in ECO mode.

This setting ranges from 5% to 10% of the nominal voltage.

Interface

Setting

06: Voltage range for ECO mode

Parameter 2: Output frequency

To set the output frequency, choose any of the following three options in 
parameter 2:

50.0Hz:

 The output frequency is set to 50.0Hz.

60.0Hz:

 The output frequency is set to 60.0Hz.

ATO:

 When selected, the output frequency will be set according to the latest 

normal utility frequency. If it ranges from 46Hz to 54Hz, the output frequency 
will be 50.0Hz.
If it ranges from 56Hz to 64Hz, the output frequency will be set at 60.0Hz. 
ATO is the default setting.

Interface

Setting

02: Output frequency settings

60 Hz, CVCF mode

Parameter 2:

 Sets low frequency point for ECO mode. 50Hz system: Ranges 

from 46.0Hz to 48.0Hz.
60Hz system: Ranges from 56.0Hz to 58.0Hz. The default value is 
48.0Hz/58.0Hz.

Parameter 3:

 Sets the high frequency point for ECO mode. 50Hz: Ranges 

from 52.0Hz to 54.0 Hz.
60Hz: Ranges from 62.0Hz to 64.0Hz. The default value is 52.0Hz/62.0Hz.

Interface

Setting

07: Frequency range for ECO mode

Parameter 2:
OPN:

 Bypass allowed. When selected, the UPS will operate in Bypass mode 

depending on the enable/disable bypass setting.

FBD:

 Bypass not allowed. When selected, the UPS will not be able to operate 

in Bypass mode under any circumstances.

Parameter 3:
ENA:

 Bypass enabled. When selected, it means that the Bypass mode is 

activated.

DIS:

 Bypass disabled. When selected, the automatic bypass may be used, 

but manual bypass is never allowed. Manual bypass allows users to manually 
operate the UPS in Bypass mode. For example, by pressing the OFF button in 
AC mode, it will cause the unit to start running in Bypass mode.

Interface

Setting

08: Bypass mode setting

Parameter 2: 

Sets the acceptable low voltage for bypass operation. Setting 

ranges from 110V to 209V, with a default value of 110V.

Parameter 3:

 Sets the acceptable high voltage for bypass operation. Setting 

ranges from 231V to 276V, with a default value of 264V.

Interface

Setting

03: Voltage range for bypass

Parameter 3: Frequency mode

Enables you to set the output frequency in either CVCF mode or no CVCF 
mode. You may choose any of the following two options in parameter 3:

CF:

 Sets the UPS in the CVCF mode. If selected, the output frequency will be 

fixed at 50Hz or 60Hz according to the setting in parameter 2. The input 
frequency could range from 46Hz to 64Hz.

NCF: 

Sets the UPS to normal mode (not CVCF mode).

If selected, the output frequency will synchronize with the input frequency 
within 46~54Hz at 50Hz or within 56~64 Hz at 60Hz according to the setting 
defined in parameter 2.
If 50Hz is selected in parameter 2, the UPS will transfer to battery mode 
provided the input frequency does not fall within 46~54Hz range. If 60Hz is 
selected in parameter 2, the UPS will transfer to battery mode provided the 
input frequency does not fall within the 56~64Hz range.
*If ATO is selected in Parameter 2, Parameter 3 will show the current frequency

50 Hz, Normal mode

ATO

Note:

 If the UPS is set to CVCF mode, the bypass function will be disabled automatically.

But when a single UPS without parallel function is powered on with utility power and before the UPS finishes the startup, there will 
be a few seconds of voltage pulse (same as the input voltage) on the bypass output.
If you need to remove the pulse on this mode to better protect your load, you could contact the dealer for help.
This situation will not happen in UPS units working on parallel mode.

Parameter 2: 

Sets the acceptable low frequency for bypass operation.

50Hz system: Setting ranges from 46.0Hz to 49.0Hz. 60Hz system: Setting 
ranges from 56.0Hz to 59.0Hz. The default value is 46.0Hz/56.0Hz.

Parameter 3:

 Sets the acceptable high frequency for bypass operation.

50Hz: Setting ranges from 51.0Hz to 54.0 Hz. 60Hz: Setting ranges from 
61.0Hz to 64.0Hz. The default value is 54.0Hz/64.0Hz.

Interface

Setting

04: Frequency range for bypass

Parameter 3:

 Enables or disables the ECO feature. You may choose between 

the following two options:

DIS:

 Disables the ECO feature

ENA: 

Enables the ECO feature

When the ECO feature is disabled, the voltage and frequency range can still 
be set for this mode, however, such parameters will take effect only if the 
ECO function has been enabled.

Interface

Setting

05: ECO mode enable/disable

Summary of Contents for FDC-106KMR-ISO

Page 1: ...2 y e a r W a r r a n t y Ajustes 07_14_2017 User manual Uninterruptible Power Supply System FDC 106KMR ISO FDC 110KMR ISO FDC 206KMR FDC 210KMR...

Page 2: ...he UPS must be thoroughly dry before being installed Failure to do so may increase the risk of electric shock Do not install the UPS system near water or in moist environments To reduce the risk of ov...

Page 3: ...f the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS...

Page 4: ...ry ground for battery pack 22 Output breaker 23 Maintenance bypass switch 24 Output control signal slot 25 Maintenance bypass ground 26 Maintenance bypass output terminals 27 Maintenance bypass UPS ou...

Page 5: ...battery pack breaker must also be set to OFF before installing the battery pack Pay close attention to the rated battery voltage marked on the rear panel If you want to change the number of batteries...

Page 6: ...VA load max Connect X1 X3 via jumper wire Connect N N via jumper wire This will give you 120V output for 10KVA load The following connection will give you two sets of 120V outputs each output takes 5K...

Page 7: ...m the selected settings of the configuration menu Turns off the UPS Press and hold this button for 0 5 second to turn off the UPS Esc key Press this button to return to the last setting of the configu...

Page 8: ...e UPS will perform an automatic battery self test on a periodic basis The default setting for the battery self test is once per week 3 Battery self test interval can also be set through the monitoring...

Page 9: ...ixed 11 Operation in fault mode 1 When the Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error in the UPS Fault codes are available via the LCD panel Refer to...

Page 10: ...re connected correctly 4 Turn on each UPS one by one and make sure that AC mode LED or Battery mode LED display is lit in each UPS Using a multimeter measure the output voltage of each UPS to make sur...

Page 11: ...he load and complete ly shut down the UPS system 2 Enable the Bypass setting in each UPS and then power off the running UPS All UPS units in the parallel system will transfer to Bypass mode Remove all...

Page 12: ...ce Setting 03 Voltage range for bypass Parameter 3 Frequency mode Enables you to set the output frequency in either CVCF mode or no CVCF mode You may choose any of the following two options in paramet...

Page 13: ...V to 5 7V the default value is 0V Interface Setting 13 Battery voltage adjustment Parameter 2 You may choose Add or Sub to adjust the charger voltage Parameter 3 The voltage ranges from 0V to 9 9V the...

Page 14: ...ress This operation is used to check the battery status 3 9 Fault codes 3 10 Warning indicators Fault event Bus start failure Bus over Bus under Bus unbalanced Inverter soft start failure High inverte...

Page 15: ...UPS is overloaded UPS is overloaded Devices connected to UPS are fed directly with utility power through Bypass After repetitive overloads the UPS is locked in Bypass mode Connected devices are fed di...

Page 16: ...utput Nominal voltage AC voltage regulation battery mode Frequency synchronized range Frequency battery mode Power factor Efficiency AC mode Efficiency battery mode Overload Transfer time line to batt...

Page 17: ......

Reviews: