Forza FDC-106KMR-ISO User Manual Download Page 7

* CVCF stands for converter mode.

Mode

LED

UPS startup
Bypass mode
AC mode
Battery mode
CVCF mode
Battery test
ECO mode
Fault

Bypass

Line

Battery

Fault

Note:     means LED is illuminated      means LED is not illuminated

2-5. ForzaTracker monitoring software

ForzaTracker is a new generation of UPS monitoring software, which provides user-friendly interface to monitor and control your 
Uninterruptible Power System. This unique software provides safe auto-shutdown for multi-computer systems during power 
failures. With this software, users can monitor and control any UPS on the same LAN no matter how far they might be from the 
UPS.

Installation procedure for Windows users:

1. Use the supplied CD or go to the website: 

http://www.forzaups.com/us/driver-downloads/

.

2. After clicking the software icon, choose the required operation system.
3. Follow the on-screen instructions to install the software.
4. When you finished downloading all required files, enter the serial No (Installation Password): 

5242-87f6-64re-di8d-986u

 to install  

    the software (include the hyphens).
5. In order to access as Administrator, input the password: 111296.
6. When your computer restarts, the management software will appear as a light blue round icon located in the system tray, near        
    the clock.
    For Mac users, please refer to the ForzaTracker quick installation guide inside the Mac folder.

3. Advanced operation
3-1. Description of buttons and functions

3-2. LED Indicators and LCD panel

There are four LEDs on front panel design to show the operation status of the UPS:

Function

Button

ON/Enter

Button

OFF/ESC

Button

Test/Up

Button

Mute/Down

Button

Test/Up +

Mute/Down

Button

Turns on the UPS

: Press and hold this button over 0.5 second to turn on the UPS.

Enter Key

: Press this button to confirm the selected settings of the configuration menu.

Turns off the UPS

: Press and hold this button for 0.5 second to turn off the UPS.

Esc key

: Press this button to return to the last setting of the configuration menu.

Battery test

: Press and hold this button for 0.5 second to test the battery status while

in AC mode, or CVCF mode.

UP key

: Press this button to display the next selection in the configuration menu.

Mutes the alarm:

 Press and hold the button for 0.5 second to mute the buzzer.

Please refer to sections below for details.

Down key

: Press this button to display previous selection in the configuration menu.

Press and hold these two buttons simultaneously for 1 second either to enter

or exit the menu settings.


LCD Panel

BYPASS

LINE

BATTERY

FAULT

OFF/ESC

TEST/UP

MUTE/DOWN

ON/ENTER

Backup

Time Info

Mode Operation

Info

Programmable

Output Info

Input & Battery

Voltage Info

Output & Battery

Voltage Info

Battery Info

Load Info

Fault

Info

Mute Operation

Display

Function

Backup time information

Fault information

Mute operation

Output & battery voltage information

Load information

Provides a digital indication of the battery discharge time.

H: hours, M: minutes, S: seconds

Indicates that a warning or fault has occurred.

Displays the fault codes, listed in detail in the sections below.

Indicates that the UPS alarm has been disabled.

Provides an indication of the output voltage, frequency or battery 

voltage. VAC: output voltage, VDC: battery voltage, Hz: frequency

Indicates the load level at 0-25%, 26-50%, 51-75%, and 76-100%

Overload indication.
Indicates the load or the output is short-circuited.

Display

Function

Backup time information

Fault information

Mute operation

Output & battery voltage information

Provides a digital indication of the battery discharge time.

H: hours, M: minutes, S: seconds

Indicates that a warning or fault has occurred.

Displays the fault codes, listed in detail in the sections below.

Indicates that the UPS alarm has been disabled.

Summary of Contents for FDC-106KMR-ISO

Page 1: ...2 y e a r W a r r a n t y Ajustes 07_14_2017 User manual Uninterruptible Power Supply System FDC 106KMR ISO FDC 110KMR ISO FDC 206KMR FDC 210KMR...

Page 2: ...he UPS must be thoroughly dry before being installed Failure to do so may increase the risk of electric shock Do not install the UPS system near water or in moist environments To reduce the risk of ov...

Page 3: ...f the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS...

Page 4: ...ry ground for battery pack 22 Output breaker 23 Maintenance bypass switch 24 Output control signal slot 25 Maintenance bypass ground 26 Maintenance bypass output terminals 27 Maintenance bypass UPS ou...

Page 5: ...battery pack breaker must also be set to OFF before installing the battery pack Pay close attention to the rated battery voltage marked on the rear panel If you want to change the number of batteries...

Page 6: ...VA load max Connect X1 X3 via jumper wire Connect N N via jumper wire This will give you 120V output for 10KVA load The following connection will give you two sets of 120V outputs each output takes 5K...

Page 7: ...m the selected settings of the configuration menu Turns off the UPS Press and hold this button for 0 5 second to turn off the UPS Esc key Press this button to return to the last setting of the configu...

Page 8: ...e UPS will perform an automatic battery self test on a periodic basis The default setting for the battery self test is once per week 3 Battery self test interval can also be set through the monitoring...

Page 9: ...ixed 11 Operation in fault mode 1 When the Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error in the UPS Fault codes are available via the LCD panel Refer to...

Page 10: ...re connected correctly 4 Turn on each UPS one by one and make sure that AC mode LED or Battery mode LED display is lit in each UPS Using a multimeter measure the output voltage of each UPS to make sur...

Page 11: ...he load and complete ly shut down the UPS system 2 Enable the Bypass setting in each UPS and then power off the running UPS All UPS units in the parallel system will transfer to Bypass mode Remove all...

Page 12: ...ce Setting 03 Voltage range for bypass Parameter 3 Frequency mode Enables you to set the output frequency in either CVCF mode or no CVCF mode You may choose any of the following two options in paramet...

Page 13: ...V to 5 7V the default value is 0V Interface Setting 13 Battery voltage adjustment Parameter 2 You may choose Add or Sub to adjust the charger voltage Parameter 3 The voltage ranges from 0V to 9 9V the...

Page 14: ...ress This operation is used to check the battery status 3 9 Fault codes 3 10 Warning indicators Fault event Bus start failure Bus over Bus under Bus unbalanced Inverter soft start failure High inverte...

Page 15: ...UPS is overloaded UPS is overloaded Devices connected to UPS are fed directly with utility power through Bypass After repetitive overloads the UPS is locked in Bypass mode Connected devices are fed di...

Page 16: ...utput Nominal voltage AC voltage regulation battery mode Frequency synchronized range Frequency battery mode Power factor Efficiency AC mode Efficiency battery mode Overload Transfer time line to batt...

Page 17: ......

Reviews: