The illustrations are indicative only. When installing accessories, refer
to the instructions supplied with the accessories themselves.
Type C33
KC 24
Minimum permissible length of vertical coaxial pipes is 1 meter, not including the first elbow connected to the boiler.
Maximum permissible length of Ø 100/60 mm vertical coaxial pipes is 10 meters not including the first elbow connected to the boiler.
Maximum permissible length of Ø 125/80 mm vertical coaxial pipes is 14.5 meters not including the first elbow connected to the boiler.
For each additional 1 meter of straight pipe maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The 100/60 mm roof coaxial terminal reduces maximum permissible length by 1.5 meters.
KC 28
Minimum permissible length of vertical coaxial pipes is 1 meter, not including the first elbow connected to the boiler.
Maximum permissible length of Ø 100/60 mm vertical coaxial pipes is 9 meters not including the first elbow connected to the boiler.
Maximum permissible length of Ø 125/80 mm vertical coaxial pipes is 13.5 meters not including the first elbow connected to the boiler.
For each additional 1 meter of straight pipe maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The 100/60 mm roof coaxial terminal reduces maximum permissible length by 1.5 meters.
fig.13
fig.13b
fig.14