TESTING THE BOILER
5.1.
Preliminary checks
Before testing the boiler, it is recommended to check the following:
- the flue gas discharge duct and the relative terminal are installed in conformity with the instructions: with the boiler operating there must
be no leakage of combustion by-products from any of the gaskets;
- the boiler is powered by a 230 V - 50 Hz mains supply;
- the system is correctly filled with water (pressure gauge reading 1 to 1.3 bar);
- any shut-off cocks in the system pipes are open;
- the gas supplied to the boiler must be of the type for which the boiler is designed. If necessary, convert the boiler following the instructions in
subsection 4.14.
Conversion to other gases types and burner adjustment
. This operation must be carried out by a qualified service engineer;
- the gas supply cock is open;
- there are no gas leaks;
- the main switch installed ahead of the boiler is turned on;
- the 3 bar safety valve is not stuck;
- there are no water leaks;
- the pump has not seized;
- the condensate trap installed on the boiler is discharging condensate correctly and is not stuck.
If the boiler not be installed in compliance with these installation instructions, current laws and standards, notify the
responsible person for the system and do not test the boiler.