INSTALLATION
ST51A/ST75A/ST75AV Mass Flow Meters
22
Fluid Components International LLC
HART Connections
Connect the installation HART wiring to the appropriate J8 terminals depending on the application.
●
Single Connection – The instrument supplies power to the loop and controls the current as well. For this application connect HART+
to J8-1 and HART- to J8-3.
●
Network (Multidrop) Connection – The instrument receives loop power from the network, and controls the current. For this
application connect E to J8-3 and EXT_HART- to J8-2.
The block diagram in
below shows the single connection and multidrop HART setups.
Use a 250 Ω 1%, ≥ 0.3 W
resistor as shown in the
diagram below only if the external HART interface/wiring does not have this resistance built-in (HART requires a minimum loop resistance of 230
Ω
).
. If using a handheld HART communicator/calibrator connect it to the line as described
by the manufacturer’s instructions.
C
ABLING
R
ECOMMENDATION
Use a shielded, twisted-pair instrument grade wire (min. 24 AWG for runs less than 5000 ft/1500 m; min. 20 AWG for longer distances). The RC
value of the wire (
Total Resistance
x
Total Capacitance
) must be less than 65 µs (not a concern for point-to-point topology with a run less than
328 ft/100 m). A cable designed for HART/RS-485 such as Belden 3105A is recommended for complex setups or particularly long runs or both.
Note:
The HART communications digital signals are superimposed on top of the channel #1 current loop (4-20 mA) output.
When HART communications is in use, the HART current loop channel #1 MUST be configured as FLOW to comply
with the HART protocol. The channel #1 current loop output is configured as FLOW by default at the factory.
Figure 19 – Single Connection and Multidrop HART Setups
C01208-1-1
ST51A/75A/75AV
HART
J8-1
J8-2
J8-3
ST51A/75A/75AV
HART
J8-1
J8-2
J8-3
ST51A/75A/75AV
HART
J8-1
J8-2
J8-3
ST51A/75A/75AV
HART
Network P.S.
24 VDC
HART
Master
J8-1
R
LOAD
HART
I/O
J8-2
J8-3
ST51A/75A/75AV
HART
HART Master
+
HART
I/O
–
J8-1
J8-3
4-
20 I
n
HART+
HART–
(a) HART Single Connection
(b) HART Network, Multidrop
Summary of Contents for ST51A
Page 1: ...Doc No 06EN003426 Rev C...
Page 83: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 75...
Page 84: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 76 Fluid Components International LLC...
Page 85: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 77...
Page 86: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 78 Fluid Components International LLC...
Page 87: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 79...
Page 88: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 80 Fluid Components International LLC...
Page 89: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 81...
Page 90: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 82 Fluid Components International LLC...
Page 91: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 83...
Page 92: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 84 Fluid Components International LLC...
Page 93: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 85...
Page 94: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 86 Fluid Components International LLC...
Page 95: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 87...
Page 96: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 88 Fluid Components International LLC...
Page 97: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 89...