ST51A/ST75A/ST75AV Mass Flow Meters
INSTALLATION
Fluid Components International LLC
7
Recommended Straight Run
For optimal flow meter performance FCI recommends a minimum of 20 pipe diameters upstream straight run and 10 pipe diameters of
downstream straight run. See
below. Where straight run is limited, FCI offers Vortab flow conditioners for use in applications that
have significant straight run limitations. FCI uses the AVAL application modeling software to predict meter performance in each installation.
AVAL outputs are available to review prior to order placement and will indicate performance expectations both with and without flow
conditioning.
Figure 4 – Recommended Straight Run (ST75A Shown)
Installing ST51A Flow Element
Compression Fitting Mounting
The ST51A is available with both Teflon compression fitting ferrules and metal ferrules. While the Teflon ferrule can be readjusted, it has a
lower process pressure rating and over-tightening may cause it to become stuck or damage the extension pipe. The metal ferrule version
can only be tightened down once and becomes permanently positioned. The ferrule type is indicated in the instrument part number
displayed on the instrument tag. This can be cross-referenced with the Ordering Information Sheet (OIS).
All flow meters have been calibrated with the flow element located at the centerline of the pipe and flow stream as shown in
Couplings and threadolets come in various dimensions. Proper installation requires that the element be measured with consideration to
process connection dimensions and pipe centerline. Install the element in the line with the compression fitting lightly tightened around the
extension, then slowly move the pipe extension forward until the element is at centerline as shown.
Caution:
Elements are shipped in a protective sleeve. After removing the sleeve, keep the element from sliding through the
compression fitting and contacting the opposing wall with any force. Hitting the pipe wall may damage the element
and upset the calibration (critical in top mount installations).
See
for instrument outline dimensional details.
C00568-3-1
* AT LEAST 20 DIAMETERS
AFTER LAST FLOW DISTURBANCE
10 DIAMETERS
BEFORE NEXT
FLOW DISTURBANCE
DIAMETER
* OPTIMUM CONDITION
FLOW
Summary of Contents for ST51A
Page 1: ...Doc No 06EN003426 Rev C...
Page 83: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 75...
Page 84: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 76 Fluid Components International LLC...
Page 85: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 77...
Page 86: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 78 Fluid Components International LLC...
Page 87: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 79...
Page 88: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 80 Fluid Components International LLC...
Page 89: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 81...
Page 90: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 82 Fluid Components International LLC...
Page 91: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 83...
Page 92: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 84 Fluid Components International LLC...
Page 93: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 85...
Page 94: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 86 Fluid Components International LLC...
Page 95: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 87...
Page 96: ...APPENDIX A DRAWINGS ST51A ST75A ST75AV Mass Flow Meters 88 Fluid Components International LLC...
Page 97: ...ST51A ST75A ST75AV Mass Flow Meters APPENDIX A DRAWINGS Fluid Components International LLC 89...