Logix
®
Digital Positioners FCD LGENIM0110-0 05/16
flowserve.com
33
Figure 29: HART DIP Switch
23.4 Burst Mode
Burst Mode is available with a handheld device. In the
handheld, select the Burst Mode feature under the
Configuration Menu. Variables that are transmitted in burst
mode are shown in the table below.
Table 15: Default HART Parameters for Burst Mode
HART
Variable
Data Description
Primary
4-20 Command (%)
Secondary
Final Command (%)
Tertiary
Purchased with Standard Diagnostics:
Temperature (C)
Purchased with Advanced or Pro
Diagnostics: Supply Pressure (bar)
Quaternary
Valve Position (%)
NOTE:
These variable assignments are reestablished
during a factory reset. A field upgrade will not change the
tertiary variable.
NOTE:
The DTM will not function while the positioner is
in Burst Mode.