Terminal Block wiring diagram for rack models
NOTE 1:
Make sure that the wires are connected tightly with the terminals.
NOTE 2:
There are two kinds of outputs: output terminal/outlets and programmable terminal. Please
connect non-critical devices to the programmable terminal and critical devices to the output terminal/outlets.
During power failure, you may extend the backup time to critical devices by setting shorter backup time for
non-critical devices.
NOTE 3:
Please install the output breaker between the output terminal and the load, and the breaker
should be qualified with leakage current protective function if necessary.
6)
Put the terminal block cover back to the rear panel of the UPS.
Warning:
(Only for standard model)
Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring
connection.
Particularly, do not try to connect the standard internal battery to the external battery. The battery type
and voltage may be different. If you connect them together, it maybe causes the hazard of electric
shock or fire!
Warning:
For standard battery pack, there are one DC breaker to disconnect the battery pack and the UPS. But
for other external battery pack, make sure a DC breaker or other protection device between UPS and
external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before
installation.
NOTE:
Set the battery pack breaker in “OFF” position and then install the battery pack.
Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the
numbers of the battery pack, please make sure you modify the setting simultaneously. The connection
with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the
battery pack is correct.
Pay highly attention to the polarity marking on external battery terminal block, and make sure the
correct battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
Make sure the protective earth ground wiring is correct. The wire current spec, color, position,
connection and conductance reliability should be checked carefully.
Make sure the utility input & output wiring is correct. The wire current spec, color, position, connection
and conductance reliability should be checked carefully. Make sure the L/N site is correct, not reverse
and short-circuited.
Input Neutral
Input Line
Ground
Output Line
Output Neutral