6. Specifications 

MODEL 

MaxiFlex 6K 

MaxiFlex 6KRM 

MaxiFlex 10K 

CAPACITY* 

6000 VA / 4800 W 

10000 VA / 8000 W 

INPUT 

Voltage 

Range 

Low Line Loss 

110 VAC ± 3 % at 50% Load; 176 VAC ± 3 % at 100% Load 

Low Line 

Comeback 

Low Line Loss V 10V 

High Line Loss 

  300 VAC ± 3 % 

High Line 

Comeback 

High Line Loss Voltage - 10V   

Frequency Range 

46Hz ~ 54 Hz @ 50Hz system 
56Hz ~ 64 Hz @ 60Hz system 

Phase 

Single phase with ground 

Power Factor 

 0.99 at 100% Load 

OUTPUT 

Output voltage 

208/220/230/240VAC 

AC Voltage Regulation   

± 1% 

Frequency Range   

46Hz ~ 54 Hz @ 50Hz system 

(Synchronized Range) 

56Hz ~ 64 Hz @ 60Hz system 

Frequency Range (Batt. Mode) 

50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz 

Overload 

AC mode 

100%~110%: 10min

110%~130%: 1min

>130% : 1sec 

Battery mode 

100%~110%: 30sec

110%~130%: 10sec

>130% : 1sec 

Current Crest Ratio 

3:1 max 

Harmonic Distortion 

 3 % @ 100% Linear Load; 

 6 % @ 100% Non-linear Load 

Transfer 

Time 

Line Battery 

0 ms 

Inverter Bypass 

0 ms 

Inverter ECO 

<10 ms 

EFFICIENCY 

AC mode 

> 89% 

Battery Mode 

> 88% 

BATTERY 

Type & Numbers 

12 V / 7 Ah x 20 

12 V / 9 Ah x 20 

Recharge Time 

7 hours recover to 90% 

capacity 

3 hours recover to 

90% capacity 

9 hours recover to 90% 

capacity 

Charging Current   

1 A ± 10% (max.) 

2 A ± 10% (max.) 

1 A ± 10% (max.) 

Charging 

Voltage   

   

273 V ± 1%   

PHYSICAL 

Dimension,   

592 X 250 X 576 

UPS unit: 580 X 438 X 

133 

592 X 250 X576 

DxWxH(mm) 

Battery pack: 580 X 

438 X 133 

Net Weight (kgs) 

81 

UPS unit: 17   

83 

Battery pack: 57 

ENVIRONMENT 

Operation Temperature 

0 ~ 40°C (the battery life will down when > 25°C) 

Operation Humidity 

<95 % and non-condensing 

Operation Altitude** 

<1000m 

Acoustic Noise Level 

Less than 55dB @ 1 Meter 

Less than 58dB @ 1 Meter 

MANAGEMENT 

Smart RS-232 or USB 

Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

 
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC. 
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m. 
***Product specifications are subject to change without further notice.   

 

 

Summary of Contents for MaxiFlex10K

Page 1: ...User Manual Uninterruptible Power Supply System MaxiFlex 6K MaxiFlex 6KRM MaxiFlex 10K...

Page 2: ...gs and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through...

Page 3: ...2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 9 2 5 SOFTWARE INSTALLATION 10 3 OPERATIONS 11 3 1 BUTTON OPERATION 11 3 2 LED INDICATORS AND LCD PANEL 11 3 3 AUDIBLE ALARM 13 3 4 SINGLE UPS OPERATION 14 3 5...

Page 4: ...tion Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip ove...

Page 5: ...disconnect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62...

Page 6: ...e user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only available for parallel model One share current cable only available for parallel model One batter...

Page 7: ...port 2 USB communication port 3 Emergency power off function connector EPO connector 4 Share current port only available for parallel model 5 Parallel port only available for parallel model 6 Intelli...

Page 8: ...3 Turn off all the connected devices before connecting to the UPS 4 Prepare wires based on the following table Model Wiring spec AWG Input Output Battery Ground Maxiflex6K 10 10 10 Maxiflex10K 8 8 8 M...

Page 9: ...e are one DC breaker to disconnect the battery pack and the UPS But for other external battery pack make sure a DC breaker or other protection device between UPS and external battery pack is installed...

Page 10: ...directly connect to the loads 4 Each UPS is connected to an independent battery pack 5 Remove the cover of parallel share current cable port on the UPS connect each UPS one by one with the parallel ca...

Page 11: ...ion Wiring diagram of parallel system for rack models 2 5 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown Diagram 4 Paralle...

Page 12: ...P key Press this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details...

Page 13: ...sabled Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 2...

Page 14: ...s Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Warning Overload Beeping twice every second No Low battery Beeping once every second Battery unconnected Over charge EPO ena...

Page 15: ...ect devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel will display total load level 2 If it is necessary to connect the inductive loads such as a print...

Page 16: ...in AC mode CVCF mode ECO mode you could press the Test button to let the UPS do battery self test 2 To keep the system reliable the UPS will perform the battery self test automatically periodically Th...

Page 17: ...e input breaker and switch off the battery breaker 4 Remove the cabinet and then modify the jumper on the control board to set the battery numbers refer to NOTE below Then disconnect battery wire for...

Page 18: ...nto bypass mode without output 2 Turn off the output breaker of this unit and then turn off the input breaker of this unit 3 After it shuts down you can turn off the battery breaker and remove the par...

Page 19: ...ers to set up the UPS Refer to following diagram Parameter 1 It s for program alternatives There are 15 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or v...

Page 20: ...ng for 50 0Hz 60 0Hz The output frequency is setting for 60 0Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output...

Page 21: ...ng range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz l 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function You may choose following two options DIS...

Page 22: ...ion is not supported by the Rack model Interface Setting Parameter 3 Set programmable output You may choose the following three options ON Programmable output is manually switched on timelessly OFF Pr...

Page 23: ...e UPS is running at normal mode and can t restart without battery l 13 Battery voltage adjustment Interface Setting Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Para...

Page 24: ...s within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at AC mode LCD display ECO mode Description When the input voltage is within voltage...

Page 25: ...y status LCD display Fault status Description When UPS has fault happened it will display fault messages in LCD panel LCD display 3 9 Fault Code Fault event Fault code Icon Fault event Fault code Icon...

Page 26: ...wice every second Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure Over temperature Beeping every second Charger failure Beeping ev...

Page 27: ...Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becom...

Page 28: ...eck if the PRA ID number is right after turning on input breakers one by one If all the number displays are correct it s ok to turn on UPSs after disabling the warning message by pressing UP and DOWN...

Page 29: ...es and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery...

Page 30: ...FICIENCY AC mode 89 Battery Mode 88 BATTERY Type Numbers 12 V 7 Ah x 20 12 V 9 Ah x 20 Recharge Time 7 hours recover to 90 capacity 3 hours recover to 90 capacity 9 hours recover to 90 capacity Chargi...

Reviews: