please visit www.flexston.com
21
l
08: Bypass mode setting
Interface
Setting
Parameter 2:
OPN
: Bypass allowed. When selected, UPS will run at Bypass
mode depending on bypass enabled/disabled setting.
FBD
: Bypass not allowed. When selected, it’s not allowed for
running in Bypass mode under any situations.
Parameter 3:
ENA
: Bypass enabled. When selected, Bypass mode is activated.
DIS
: Bypass disabled. When selected, automatic bypass is
acceptable, but manual bypass is not allowed. Manual bypass
means users manually operate UPS for Bypass mode. For
example, pressing OFF button in AC mode to turn into Bypass
mode.
l
09: Battery backup time setting
Interface
Setting
Parameter 3:
000~999:
Set the maximum backup time from 0min to 999min.
UPS will shut down to protect battery after backup time arrives.
The default value is 990min.
DIS:
Disable battery discharge protection and backup time will
depend on battery capacity.
l
10: Programmable output setting
Note
:
This function is not supported by the Rack model.
Interface
Setting
Parameter 3:
Set programmable output. You may choose the
following three options:
ON:
Programmable output is manually switched on timelessly.
OFF:
Programmable output is manually switched off. However, if
UPS restarts, this setting will automatically go to “ATO” status.
ATO:
Programmable output is automatically turned on or cut off
according to battery or load status. When the battery voltage is
lower than the setting point, or shutdown time arrives, the
programmable output will be cut off automatically. After the utility
is recovering, the output will turn on automatically. If overload
happens, the programmable output also will be cut off
automatically. If it happens 3 times, the programmable output will
be cut off until it is manually switched on.
l
11: Shutdown point for programmable output
Note
:
This function is not supported by the Rack model.
Interface
Setting
Parameter 2: 001.
Set shutdown time for programmable output.
Parameter 3: Shutdown time in minutes.
Setting range is from 0 to 300. When shutdown time arrives, the
programmable output terminal will be cut off. The default value is
30 minutes.