background image

ENGLISH

9PX 700 RT
9PX 1000 RT
9PX 1000GRT
9PX 1500 RT
9PX 1500GRT
9PX 2000 RT
9PX 2200 GRT
9PX 3000 RT
9PX 3000 GRT
9PX 3000 GLRT
9PX EBM 36V RT
9PX EBM 48V RT
9PX EBM 72V RT

Installation  
and user manual

Copyright © 2016 

EATON

 

All rights reserved.

9PX 1-3 KVA US_EN

Questo manuale d’istruzione è fornito da trovaprezzi.it. Scopri tutte le offerte per 

Eaton 9PX 1000i

RT2U

 o cerca il tuo prodotto tra le 

migliori offerte di Gruppi di Continuità

Summary of Contents for 9PX 1000 RT

Page 1: ...X 3000 GLRT 9PX EBM 36V RT 9PX EBM 48V RT 9PX EBM 72V RT Installation and user manual Copyright 2016 EATON All rights reserved 9PX 1 3 KVA US_EN Questo manuale d istruzione è fornito da trovaprezzi it Scopri tutte le offerte per Eaton 9PX 1000i RT2U o cerca il tuo prodotto tra le migliori offerte di Gruppi di Continuità ...

Page 2: ...io communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Special symbols The following are examples of symbols used on the UPS or accessories to alert you to important information RISK OF ELECTRIC SHOCK Observe the warning associated with the risk of electric sh...

Page 3: ...ihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit Product safety To connect the UPS instructions and operation described in the manual must be followed in the indicated order CAUTION To reduce the risk of fire the unit connects only to a circuit provided with 20...

Page 4: ...ormal storage temperature less than 25 C This charges the battery thus avoiding possible irreversible damage During the replacement of the Battery Module it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety If there are any questions don t hesitate to contact your EATON representati...

Page 5: ...tion ports 28 4 2 UPS remote control functions 29 4 3 Eaton Intelligent Power Software suite 31 5 Operation 5 1 Start up and Normal operation 32 5 2 Starting the UPS on Battery 32 5 3 UPS Shutdown 32 5 4 Operating modes 32 5 5 Return of AC Input Power 33 5 6 Setting High Efficiency mode 33 5 7 Configuring Bypass settings 33 5 8 Configuring battery settings 34 5 9 Retrieving the Event log 34 5 10 R...

Page 6: ...prises over 50 of recycled cardboard Sacks and bags are made of polyethylene Packing materials are recyclable and bear the appropriate identification symbol 01 PET Materials Abbreviations Number in 01 PET the symbols Polyethylene terephthalat PET 01 High density polyethylene HDPE 02 Polyvinyl chloride PVC 03 Low density polyethylene LDPE 04 Polypropylene PP 05 Polystyrene PS 06 Follow all local re...

Page 7: ...disturbances and guard the integrity of your equipment Providing outstanding performance and reliability the Eaton 9PX s unique benefits include True online double conversion technology with high power density utility frequency independence and generator compatibility ABM technology that uses advanced battery management to increase battery service life optimize recharge time and provide a warning ...

Page 8: ...RT 42 5 19 3 17 7 x 17 3 x 3 4 450 x 440 x 86 5 9PX1500GRT 41 4 18 8 17 7 x 17 3 x 3 4 450 x 440 x 86 5 9PX2000RT 61 6 27 9 23 8 x 17 3 x 3 4 605 x 440 x 86 5 9PX2200GRT 59 7 27 1 23 8 x 17 3 x 3 4 605 x 440 x 86 5 9PX3000RT 63 28 6 23 8 x 17 3 x 3 4 605 x 440 x 86 5 9PX3000GRT 61 2 27 8 23 8 x 17 3 x 3 4 605 x 440 x 86 5 9PX3000GLRT 61 27 7 23 8 x 17 3 x 3 4 605 x 440 x 86 5 9PXEBM36RT 48 1 21 8 ...

Page 9: ... Slot for optional communication card 3 Relay output contact 4 Connector for additional battery module 5 Primary group outlets for connection of critical equipment 6 Group 1 programmable outlets for connection of equipment 7 Group 2 programmable outlets for connection of equipment 8 Connector for automatic recognition of an additional battery module 9 RS232 communication port 10 USB communication ...

Page 10: ...atic recognition of battery modules 9PX EBM 72V 13 13 12 12 2 3 Accessories Part number Description 9PXEBM36RT2U 9PXEBM48RT2U 9PXEBM72RT2U Extended battery module 9RK Rack kit 9PX Network MS Network card Modbus MS Modbus and network card Relay MS Relay card BINTSYS Battery Integration System EBMCBL36 2m cable 36V EBM EBMCBL48 2m cable 48V EBM EBMCBL72 2m cable 72V EBM ...

Page 11: ... 1EBM 100 2 7kW 3 0kVA Efficiency 94 Escape Up Down Enter On Off button Battery mode indicator orange Bypass mode indicator orange The following table shows the indicator status and description Indicator Status Description Green On The UPS is operating normally on Online or on High Efficiency mode Orange On The UPS is on Battery mode Orange On The UPS is on Bypass mode Red On The UPS has an active...

Page 12: ...t is not powered until button is pressed Online mode The UPS is operating normally The UPS is powering and protecting the equipment Battery mode 1 beep every 10 seconds A utility failure has occured and the UPS is on Battery mode The UPS is powering the equipment with the battery power Prepare your equipment for shutdown End of backup time 1 beep every 3 seconds The UPS is on Battery mode and the ...

Page 13: ...ettings Sets battery configuration Com settings Sets communication parameters Event log Event filter Selects faults alarms and or events to display Event list Displays the events stored Reset event list Clears events Fault log Fault list Displays the faults stored Reset fault list Clears faults Identification Product type model Part Serial number UPS NMC firm ware Com card IPv4 Com card IPv6 Com c...

Page 14: ...larm occurs 102 On Off settings Start Restart Cold start Auto restart Auto start Start on bypass Cold start Auto restart are Enabled Auto start Start on bypass are Disabled Forced reboot Enabled Disabled Timer 10s 180s When mains recover during a shutdown sequence If set to Enabled shutdown sequence will complete and wait 10 seconds prior to restart If set to Disabled shutdown sequence will not co...

Page 15: ...nual battery set Auto detection Using standard EBM UPS detects automatically the number of EBM connected Deep Disch protect Yes No If set toYes the UPS automatically prevents battery from deep discharge by adapting end of back up time voltage threshold Warranty void if set to No Yes Com settings Input signals ROO RPO DB9 4 Sets Input signals parameters function delay operation through external con...

Page 16: ...elay Bypass DB9 1 Low bat DB9 7 UPS OK DB9 8 On bat Remote command Enabled Disabled If Enabled shutdown or restart commands from software are authorized Enabled Shutdown commands Send CMD Output OFF OFF delay restart Sets events or fault that will actuate Output signal parameters through external contact connector or RS232 port Send CMD Yes No Output OFF No UPS Group 1 Group 2 Group 1 Group 2 OFF ...

Page 17: ...as passed and the batteries were never recharged do not use the UPS Contact your service representative 3 2 Checking the accessory kit 9PX 700RT 9PX 1000RT 9PX 1500RT 9PX 2000RT 9PX 3000RT 3 Installation 14 25 26 24 27 20 21 23 22 17 18 14 9PX UPS 17 RS232 communication cable 18 USB communication cable 20 Manual CD ROM 21 Software leaflet 22 Safety instructions 23 Quick start 24 Mounting kit for 1...

Page 18: ...n cable 18 USB communication cable 19 3 cable locking systems 20 Manual CD ROM 21 Software leaflet 22 Safety instructions 23 Quick start 24 Mounting kit for 19 inch enclosures 25 2 supports for tower position Elements supplied depending on the version or optional 26 NMC communication card optional standard on Network Bundle models 27 HotSwap MBP module optional 28 Connection cables between HotSwap...

Page 19: ...ion cable 18 USB communication cable 19 Cable locking system 20 Manual CD ROM 21 Software leaflet 22 Safety instructions 23 Quick start 24 Mounting kit for 19 inch enclosures 25 2 supports for tower position Elements supplied depending on the version or optional 26 NMC communication card optional standard on Network Bundle models Verify that the following additional items are included with the UPS...

Page 20: ... with attached battery detection cable 2 Stabilizer bracket 4 screws included 3 Rack kit for 19 inch enclosures optional 4 EBM Installation manual Discard the EBM user s guide if you are installing the EBM with a new UPS at the same time Use the UPS user s guide to install both the UPS and the EBM If you ordered other UPS accessories refer to specific user manuals to check the packing contents ...

Page 21: ...h left cover toward to right direction 3 Open the left side of the front panel A ribbon cable connects the LCD control panel to the UPS Do not pull on the cable or disconnect it A small amount of arcing may occur when connecting the internal batteries This is normal and will not harm personnel Connect the cables quickly and firmly 4 Connect the two battery connectors together 5 Put back the front ...

Page 22: ...lug the EBM power cable s into the battery connector s Up to 4 EBMs may be connected to the UPS 2 Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable 3 Connect the battery detection cable s to the connector of the UPS and of the EBM s 3 5 Connecting other accessories If you ordered other UPS accessories refer to user manuals to check the c...

Page 23: ...LCD panel If you ordered other UPS accessories refer to specific user manuals to check the tower installation with the UPS To install the cabinet 1 Place the UPS on a flat stable surface in its final location 2 Always keep 6 or 150 mm of free space behind the UPS rear panel for ventilation 3 If installing additional cabinets place them next to the UPS in their final location ...

Page 24: ... KVA US_EN 3 7 Rack installation Rack mounting of UPS EBM and accessory modules Follow steps 1 to 4 for module mounting on the rails 3 3 4 4 2 1 1 The rails and necessary hardware are supplied by EATON 3 Installation ...

Page 25: ...16 It is preferable to connect the priority loads to the outlets marked 5 and the non priority loads to the outlets marked 6 7 that can be programmed Connect any high power devices to the 16 A outlet To program shutdown of outlets 6 7 during operation on battery power and thus optimise the available backup time please check the in out settings 3 For G models fit the cable locking system 19 that pr...

Page 26: ...S input cable 1 to the UPS Input socket 35 on the HotSwap MBP module 3 Connect the UPS outlet 5 to the UPS Output 34 on the HotSwap MBP module using the cable 28 supplied for G models These cables and the connectors are marked in red 4 Connect the equipment to the outlets 29 on the HotSwap MBP module These outlets differ depending on the version of the HotSwap MBP module Caution when using HotSwap...

Page 27: ... MBP do not use UPS outlets to directly power equipment As operating the bypass switch 33 will cut supply voltage to the equipment HotSwap MBP module operation 32 33 31 UPS start up with the HotSwap MBP module 1 Check that the UPS is correctly connected to the HotSwap MBP module 2 Set switch 33 to Normal position 3 Start the UPS by pressing the ON OFF button on the UPS control panel The load is su...

Page 28: ...cation cards 2 It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 2 secured by screws 2 Insert the communication card in the slot 3 Secure the card cover with the 2 screws Characteristics of the contact RS232 communication port 1 6 7 8 9 300 Ohm R 2 3 4 5 Pin Signal Direction Function 1 Bat Low Output Low Battery Output 2 TxD Output Transmit to e...

Page 29: ...ly Warning Signal inputs have no function by default please choose a function through the LCD Settings Com settings Input signals on page 15 See below 2 examples of configuration with RPO terminal used as RPO function and ROO terminal use as ROO function Remote Power Off RPO RPO is used to shutdown the UPS remotely when the contact is open This feature can be used for shutting down the load and th...

Page 30: ... described procedures 6 Activate the external remote shut down contact to test the function Always test the RPO function before applying your critical load to avoid accidental load loss Programmable Signal Outputs The 9PX incorporates 4 programmable signal outputs one relay output three optocouplers outputs pin 1 7 8 Signal outputs can be configured see Settings Com settings Output Signals on page...

Page 31: ...twork management Relay MS card has isolated dry contact Form C relay outputs for UPS status Utility failure Battery low UPS alarm OK or on Bypass Relay MS card Network MS card ETHERNET 100M 10M UPS data Reset Setting Sensor Modbus MS card ETHERNET 100M 10M UPS data Reset Setting Sensor 4 3 Eaton Intelligent Power Software suite Eaton Intelligent Power Software suite is available from eaton com dow...

Page 32: ...es power to your equipment 2 Check the UPS front panel display for active alarms or notices besides the Battery mode notice and notices that indicate missing utility power Resolve any active alarms before continuing See Troubleshooting on page 39 Check the UPS status from the front panel to view the active alarms Correct the alarms and restart if necessary 5 3 UPS Shutdown To shut down the UPS 1 P...

Page 33: ...PS restarts automatically when AC input power returns unless the restart function has been disabled and the load is supplied again 5 6 Setting High Efficiency mode In High Efficiency mode the UPS operates normally on Bypass and transfers to Online or Battery mode in less than 10 ms when utility fails Transfers to High Efficiency mode will be active after 5 minutes of Bypass voltage monitoring if B...

Page 34: ...y tests are done every week in constant charging mode and at each cycle in ABM mode The tests frequency can be modified During the test the UPS transfers to Battery mode and discharges the batteries for 10 seconds under load Battery mode is not displayed and battery low alarm does not activate during a battery test The battery test may be postponed due to bad conditions or failed if battery is not...

Page 35: ...or a long period recharge the battery every 6 months by connecting the UPS to utility power The internal batteries charge to 90 capacity in less than 3 hours However Eaton recommends that the batteries charge for 48 hours after long term storage Check the battery recharge date on the shipping carton label If the date has passed and the batteries were never recharged do not use them Contact your se...

Page 36: ...f batteries or battery packs Contact your service representative to order new batteries Proper disposal of batteries is required Refer to your local codes for disposal requirements Never dispose of batteries in a fire Batteries may explode when exposed to flame Do not open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes and may be extremely toxic Determine...

Page 37: ...place the EBM s 1 Unplug the EBM power cable and battery detection cable from the UPS If additional EBM s are installed unplug the EBM power cable and battery detection cable from each EBM 2 Replace the EBM s See Recycling the used equipment on page 38 for proper disposal A small amount of arcing may occur when connecting an EBM to the UPS This is normal and will not harm personnel Insert the EBM ...

Page 38: ...en the HotSwap MBP module and the UPS 3 Set switch 33 to Normal position The red LED on the HotSwap MBP module goes OFF 6 6 Recycling the used equipment Contact your local recycling or hazardous waste center for information on proper disposal of the used equipment Do not dispose of the battery or batteries in a fire Batteries may explode Proper disposal of batte ries is required Refer to your loca...

Page 39: ...ry mode and the battery is running low This warning is approximate and the actual time to shutdown may vary significantly Depending on the UPS load and number of Extended Battery Modules EBMs the Battery Low warning may occur before the batteries reach 20 capacity LED is On 1 beep every 3 seconds No battery The batteries are disconnected Verify that all batteries are properly connected If the cond...

Page 40: ...re nearing the end of their useful life See 6 3 When to replace batteries 7 2 Silencing the alarm Press the ESC Escape button on the front panel display to silence the alarm Check the alarm condition and perform the applicable action to resolve the condition If the alarm status changes the alarm beeps again overriding the previous alarm silencing 7 3 Service and support If you have any questions o...

Page 41: ...3000VA Table 3 Weights and dimensions Model UPS Dimensions D x W x H inch mm Weight lb kg 9PX700RT 17 7 x 17 3 x 3 4 450 x 440 x 86 5 36 4 16 5 9PX1000RT 17 7 x 17 3 x 3 4 450 x 440 x 86 5 36 4 16 5 9PX1000GRT 17 7 x 17 3 x 3 4 450 x 440 x 86 5 38 6 17 5 9PX1500RT 17 7 x 17 3 x 3 4 450 x 440 x 86 5 42 5 19 3 9PX1500GRT 17 7 x 17 3 x 3 4 450 x 440 x 86 5 41 4 18 8 9PX2000RT 23 8 x 17 3 x 3 4 605 x ...

Page 42: ...00V 110V 120V 125V 100 138V 9PX1000RT 120V 8 3A 9PX1500RT 120V 12 5A 9PX2000RT 120V 16A 9PX3000RT 120V 24A 9PX1000GRT 208V 4 8A 200V 208V 220V 230V 240V 176 276V 9PX1500GRT 208V 7 2A 9PX2200GRT 208V 10 57A 9PX3000GRT 208V 14 42A 9PX3000GLRT 208V 14 42A Table 5 Electrical input connections Model Input connection Input cable 9PX700RT NEMA 5 15P 8ft 2 4m 9PX1000RT 9PX1500RT 9PX2000RT 5 20P 8ft 2 4m 9...

Page 43: ...g or configurable as a frequency converter Output overload Online mode 102 130 12s 130 150 2s 150 shutdown after 300ms Percent is based on nominal Watt VA Transfer behavior can change see output mode setting on page 14 Battery mode 102 130 12s 130 2s Overload warning then transfer to stop output Output overload Bypass mode 102 110 Overload warning 110 130 shutdown after 5mins 130 150 shutdown afte...

Page 44: ...ransit temperature 25 to 55 C 13 to 130 F Relative humidity 0 to 96 no condensing Operating altitude Up to 3 000 meters 9 843 ft above sea level no derating for 35 c 95 F room temperature Transit altitude Up to 10 000 meters 32 808 ft above sea level Audible noise 47 dBA at 1 meter typical for 2K et 3K models 40 dBA at 1 meter typical for 70 1K et 1K5 models 9PX1000GRT 9PX 1500GRT 9PX2200GRT 9PX30...

Page 45: ... on battery power Load Devices or equipment connected to the UPS output HE mode Operating mode by which the load is supplied directly by the AC source if it is within the tolerances defined by the user This mode reduces the consumption of electrical power Manual bypass Rotary switch controlled by the user used to connect the loads directly to the AC source Transfer of the load to the manual bypass...

Page 46: ...Page 46 9PX 1 3 KVA US_EN ...

Reviews: