background image

please visit www.flexston.com 

17 

(typical 1V) with multimeter. If the difference is more than 2V, please check that parallel cable or 
share current cable are connected well. If they are all connected well, maybe it’s UPS internal issue. 
Please contact your local distributor or service center for help.   

6)  Turn  off  each  UPS  in  turns  and  after  all  of  them  transfer  to  Bypass  mode,  turn  on  the  output 

breaker of each unit. 

7)  Turn on the UPSs in the AC mode and then the parallel system connection is complete.   

2. Add one new unit into the parallel system 

1)    You can not add one new unit into the parallel system when whole system is running. You must cut 

off the load and shutdown the system.   

2)    Make sure all of the UPS are the parallel models, and follow the wiring refer to section 2-3. 

3)    Install the new parallel system refers to the previous section. 

3. Remove one unit from the parallel system 

There are two methods to remove one unit from the parallel system: 
First method: 

1)

 

Press the “OFF” key twice and each time should last for more than 0.5s. Then, the UPS will enter 
into bypass mode without output.   

2)

 

Turn off the output breaker of this unit, and then turn off the input breaker of this unit. 

3)

 

After it shuts down, you can turn off the battery breaker and remove the parallel cable and share 
current cable. Then, remove the unit from the parallel system. 

Second method:

 

1)    If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the 

load and shut down the system.   

2)    Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UPSs 

will transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance 
switches from “UPS” to “BPS”.    Turn off the input breakers and battery breakers.   

3)    Remove the UPS that you want. 

4)    Turn on the input breaker of the remaining UPSs and the system will transfer to Bypass mode.   

5)    Set the maintenance switches from “BPS” to “UPS and put the maintenance bypass covers back. 

Turn on the remaining UPSs and finish the parallel system connection.   

 

Warning: 

(Only for the parallel system) 

 Before turning on the parallel system to activate inverter, make sure that all  unit’s maintenance 

switch at the same position. 

 When parallel system is turned on to work through inverter, please do not operate the maintenance 

switch of any unit. 

Summary of Contents for MaxiFlex10K

Page 1: ...User Manual Uninterruptible Power Supply System MaxiFlex 6K MaxiFlex 6KRM MaxiFlex 10K...

Page 2: ...gs and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through...

Page 3: ...2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 9 2 5 SOFTWARE INSTALLATION 10 3 OPERATIONS 11 3 1 BUTTON OPERATION 11 3 2 LED INDICATORS AND LCD PANEL 11 3 3 AUDIBLE ALARM 13 3 4 SINGLE UPS OPERATION 14 3 5...

Page 4: ...tion Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip ove...

Page 5: ...disconnect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62...

Page 6: ...e user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only available for parallel model One share current cable only available for parallel model One batter...

Page 7: ...port 2 USB communication port 3 Emergency power off function connector EPO connector 4 Share current port only available for parallel model 5 Parallel port only available for parallel model 6 Intelli...

Page 8: ...3 Turn off all the connected devices before connecting to the UPS 4 Prepare wires based on the following table Model Wiring spec AWG Input Output Battery Ground Maxiflex6K 10 10 10 Maxiflex10K 8 8 8 M...

Page 9: ...e are one DC breaker to disconnect the battery pack and the UPS But for other external battery pack make sure a DC breaker or other protection device between UPS and external battery pack is installed...

Page 10: ...directly connect to the loads 4 Each UPS is connected to an independent battery pack 5 Remove the cover of parallel share current cable port on the UPS connect each UPS one by one with the parallel ca...

Page 11: ...ion Wiring diagram of parallel system for rack models 2 5 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown Diagram 4 Paralle...

Page 12: ...P key Press this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details...

Page 13: ...sabled Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 2...

Page 14: ...s Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Warning Overload Beeping twice every second No Low battery Beeping once every second Battery unconnected Over charge EPO ena...

Page 15: ...ect devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel will display total load level 2 If it is necessary to connect the inductive loads such as a print...

Page 16: ...in AC mode CVCF mode ECO mode you could press the Test button to let the UPS do battery self test 2 To keep the system reliable the UPS will perform the battery self test automatically periodically Th...

Page 17: ...e input breaker and switch off the battery breaker 4 Remove the cabinet and then modify the jumper on the control board to set the battery numbers refer to NOTE below Then disconnect battery wire for...

Page 18: ...nto bypass mode without output 2 Turn off the output breaker of this unit and then turn off the input breaker of this unit 3 After it shuts down you can turn off the battery breaker and remove the par...

Page 19: ...ers to set up the UPS Refer to following diagram Parameter 1 It s for program alternatives There are 15 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or v...

Page 20: ...ng for 50 0Hz 60 0Hz The output frequency is setting for 60 0Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output...

Page 21: ...ng range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz l 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function You may choose following two options DIS...

Page 22: ...ion is not supported by the Rack model Interface Setting Parameter 3 Set programmable output You may choose the following three options ON Programmable output is manually switched on timelessly OFF Pr...

Page 23: ...e UPS is running at normal mode and can t restart without battery l 13 Battery voltage adjustment Interface Setting Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Para...

Page 24: ...s within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at AC mode LCD display ECO mode Description When the input voltage is within voltage...

Page 25: ...y status LCD display Fault status Description When UPS has fault happened it will display fault messages in LCD panel LCD display 3 9 Fault Code Fault event Fault code Icon Fault event Fault code Icon...

Page 26: ...wice every second Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure Over temperature Beeping every second Charger failure Beeping ev...

Page 27: ...Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becom...

Page 28: ...eck if the PRA ID number is right after turning on input breakers one by one If all the number displays are correct it s ok to turn on UPSs after disabling the warning message by pressing UP and DOWN...

Page 29: ...es and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery...

Page 30: ...FICIENCY AC mode 89 Battery Mode 88 BATTERY Type Numbers 12 V 7 Ah x 20 12 V 9 Ah x 20 Recharge Time 7 hours recover to 90 capacity 3 hours recover to 90 capacity 9 hours recover to 90 capacity Chargi...

Reviews: