31
GATEWAY SPECIFICATION - WebdynPulse
WebdynPulse – Gateway specification - Version 2.0
Where:
Index_IO_N
Unique index of the variable:
1 to N
number_IO_N
Number of the input/output:
1 to 4 for the analogue input type
1 to 4 for the bang-bang input type
1 to 2 for the output type
1 to 2 for the index type.
type_IO_N
Type of input/output:
1: analogue input (0–10 V or 4–20 mA)
2: bang-bang input
3: switching relay output
4: pulse counting input.
name_IO_N
Name of the input/output
coeffA_N and coeffB_N
Physical conversion coefficients.
action_N
0: variable not collected
4: instantaneous variable
8: alarm
The file generated by default is:
prefixID
_IO.ini
1;1;2;PULSE1;1;0;8
2;2;5;PULSE2;1;0;4
3;3;6;PULSE3;1;0;4
7.4 Configuration via the local web interface
Input configuration via the local web interface is accessible via the menu: