8 Electrical installation
The provision of power supply, (protective) ground wire connection and line protection must be
made in accordance with the local regulations (responsible power company) and the applicable
National standards. The required electrical information can be found on the product label at the
side of the FlexFiller Direct G4, the terminal plan (labelling) and in “Appendix 3.” Terminal plan.
The FlexFiller Direct G4 has been supplied with the correct power supply cable and it is highly
recommended to use the cable provided.
All electrical connections should be carried out by a qualified and authorized electrician
in accordance with the latest issue of the IET regulations. The equipment must be
earthed. It is strongly recommended that a high sensitivity differential switch (30mA)
(residual current device RCD) is fitted on the incoming electrical supply.
Do not remove covers without first ensuring that the electrical supply is suitably isolated
and cannot be switched on.
Do not attempt to supply electricity to the equipment unless the protective covers are
correctly fitted and held securely in place.
Cables connected to the controller volt free contacts may be supplied from another
source and may remain live after the unit is isolated. These must be isolated elsewhere.
The user or the installer is responsible for the installation of the correct earthing and
protection according to valid national and local standards. All operations must be carried
out by a qualified electrician
The Flamco equipment must be connected to a mains isolator switch with a contact gap of at least 3
m. It is recommended the switch should be installed within 2m of the equipment.
8.1 Alarm installation
The installation, data processing and commissioning must be performed by a Qualified Person. The
appropriate national standards, regulations and rules must be followed.
•
Additional cables are not included or supplied by Flamco
•
Flamco recommends the use of twisted single pair shielded cable.
•
The termination resistor has a value of 120 Ohm.
•
The maximum permissible length of cables is 30m.
If controller powered down, than the is P27 normally open
If controller is powered up, than the is P27 normally closed
If controller is in error, than the is P27 normally open
For additional information on how to connect the the Flexfiller Direct to the internet or
BMS, see Flextronic connectivity guide.
P27
COM
NO
NC
Building
management
system
BMS
Summary of Contents for FlexFiller Direct G4
Page 1: ...www flamcogroup com manuals FlexFiller Direct G4 ENG Installation and operating manual...
Page 33: ...We reserve the right to change designs and technical specifications of our products 33 ENG...
Page 34: ...Manual FlexFiller Direct G4 34...
Page 35: ...We reserve the right to change designs and technical specifications of our products 35 ENG...