Shipping and Storage
MultiMAXX HE
14
FläktGroup DC-2011-0142-GB 2018-05/R5 • Subject to modifications
3
Shipping and Storage
3.1
Delivery
Manufacturer’s instructions regarding shipping and storing of the unit must be followed
(see labels on the packing).
•
Upon receipt of the Multi
MAXX
HE unit and prior to unloading, inspect the unit for
damage and verify that the shipment is complete
(refer to "Unit configuration and scope of supply" on page 9) as specified in the
freight bill.
•
If required, take photographs of all visible transit damage.
3.2
Transport
•
Attach lifting gear to the designated points of the assembly unit.
•
Chains/slings should not be knotted and/or be exposed to sharp edges.
•
The weight must be evenly distributed!
•
Only lifting gear with sufficient load carrying capacity is allowed.
•
Never use damaged lifting equipmet.
•
For your own safety wear gloves and safety footwear when hoisting or shipping the
unit
3.3
Storage
Protect the Multi
MAXX
HE unit from humidity and dirt. The unit must be stored in
a weather-proof manner indoors in accordance with class IE12 and EN 60 721-3-1
standard.
NOTE!
Missing parts or claims of shipping damage must only be reported to the transport
insurance, if the damage has been confirmed by the delivering carrier.
NOTE!
We recommend to keep the Multi
MAXX
HE in its original packaging for protection,
ease of handling, shipping and storage. Remove the original packaging only before
installation. The packaging poses a health risk and must be disposed of in accord-
ance with the relevant regulations and be kept out of reach of children. If the unit is
stored for a period of time before installation or commissioning, it must be protected
from damage through elements, build-up of dust and dirt!
DANGER DUE TO OVERHEAD LOADS!
Do not suspend or move Multi
MAXX
HE unit heater overhead.
PERSONAL INJURY!
– Do not use damaged transport devices.
– Use a fork lift truck only if the electric heater is located on a pallet.
NOTE!
Allowable storage conditions / allowable air condition for uninstalled units:
Air temperature:
-25 °C to +40 °C
Air humidity:
between 50 and 85 % (relative humidity with no condensation)
Fig. 3-1: Transport