MultiMAXX HE
Technical Description
FläktGroup DC-2011-0142-GB 2018-05/R5 • Subject to modifications
11
Tab. 2-2:
Unit dimensions
2.5
Specifications
Tab. 2-3: Specifications
* Sound pressure: standard values at 5 m distance to the unit side, at maximum air flow rate and low reflection room. Industrial hall volume
1500 m
3
, absorption surface 200 m
2
Sabin, hemispherical radiation = direction coefficient 2. These values can be significantly influenced by the
indoor characteristics in a positive or negative way.
Size / unit model size
1
2
4
A [mm]
642
738
1026
B [mm]
520
616
904
C [mm]
387
387
452
E (wide wing fan) [mm]
60
81
112
E (sickle-blade fan) [mm]
-
50
-
G [mm]
418
514
802
H [mm]
451
547
835
I [mm]
300
300
400
M [mm]
470
566
854
Model size
Speed Air
fow
rate
V
L
Heating capacity Q
T
Air
heating
at max.
heating
duty
T
Voltage
U
Max.
rated
current
l
Motor
power
consump-
tion
Motor
current
con-
sump-
tion l
Sound
power
Sound
pres-
sure *
Weight
without
louvre
Max.
Speed
1
2
3
[min
-1
]
[m3/h]
[kW] [kW] [kW] [kW]
[K]
[V]
[A]
[kW]
[A]
[dB(A)]
[dB(A)]
[kg]
A - 3 ~ 400 V 2-speed (low speed range)
1
670
1410
12
4
8
12
26
3x400
17.3
0.03
0.05
55
40
28
860
1620
23
0.05
0.10
61
46
2
710
2260
21
7
14
21
27
30.3
0.07
0.14
61
46
34
910
2710
23
0.12
0.30
65
50
4
500
4610
42
14
28
42
27
60.6
0.15
0.30
59
44
69
650
6480
19
0.24
0.59
68
53
B - 3 ~ 400 V 2-speed (high speed range)
1
1050
1990
12
4
8
12
18
3x400
17.3
0.03
0.14
67
52
28
1320
2470
15
0.14
0.25
71
56
2
890
3010
21
7
14
21
21
30.3
0.19
0.29
69
54
34
1270
3980
16
0.29
0.50
76
61
4
740
8340
42
14
28
42
15
60.6
0.37
0.61
81
66
69
910
9900
13
0.51
1.00
76
61
V - 3 ~ 500 V 3-speed
2
700
1970
12.2
6.1
9.15
12.2
18
3x500 14.0
0.07
0.14
55
43
36
1070
2870
13
0.26
0.34
67
52
1370
3810
10
0.34
0.50
75
60