Servicing and Maintenance
MultiMAXX HE
34
FläktGroup DC-2011-0142-GB 2018-05/R5 • Subject to modifications
Overview of regular maintenance intervals
The following maintenance intervals must be observed within the specified periods.
7.3
Quarterly maintenance
7.3.1 Filter replacement
In case of reduced air flow of the unit heater its filter should be inspected and, if nec-
essary, replaced or cleaned.
If the filter assembly of the unit is fitted with a differential pressure switch, the relevant
value must be set (not performed by the factory). A signal lamp on the OSHE control
cabinet is used to indicate if the filter needs to be replaced.
Use the type code on page 3 for ordering a spare filter.
Maintenance
intervals
Components
Qu
arterly
T
w
ice a yea
r
Annually
Checking air filter* (dirt, damage, odour)
x
Checking air intake openings / grilles*
x
Checking air discharge openings / grilles*
x
Checking fans or fan sections*
x
Checking electrical connections
x
Checking earthing
x
* If necessary, clean and remove foreign objects or replace
Tab. 7-1:
Regular maintenance
Pos. 1: Roof intake hood
Pos. 2: G2 or G4 bag filter
•
Remove lateral screws and open the top
section of the air intake hood.
•
Remove and replace the bag filter
•
Close the hood and tighten the screws
Fig. 7-1:
Roof intake hood: ZHx.350x
1
2