Installation Instruction
23.1.07
Panda_12mini_PMS_Digital_s00865_Installation manual.V02 - Chapter D: Installation Instruction Page 69
D.6.3 Connection of the fuel lines at the tank
Lead the return fuel pipe connected to the day tank to the floor
The return pipe connected to the tank must be dropped to the same depth as the suction pipe, if
the generfator is mounted higher than the tank, in order to prevent fuel running back into the tank
after the motor has been switched off, which can lead to enormous problems if the generator is
switched off for a long period.
Non-return Valve in the Suction Pipe
A non-return valve must be fitted to the suction pipe, which prevents the fuel flowing back after the
generator has been switched off, if it is not possible to use the return flow pipe as a submerge
pipe be placing it in the tank. The instructions "Bleeding Air from the Fuel System" must be read
after initial operation or after it has stood still for a long period, in order to preserve the starter bat-
tery.
ATTENTION! Non-return valve for the fuel return pipe
If the fuel tank should be installed over the level of the generator (e.g. daily tank), then a
non-return valve must be installed into the fuel return pipe to guaranteed that through the
return pipe no fuel is led into the injection pump.
D.6.4 Position of the pre-filter with water separator
Additionally to the standard fine filter a pre-
filter with water separator must be installed
outside of the sound cover in the fuel sys-
tem line. (is not included in delivery.)
Fig. D.24: Fuel filter with water separator