Generator Failure
23.1.07
Panda_12mini_PMS_Digital_s00865_Installation manual.V02 - Chapter C: Generator Failure Page 49
1. Fuel solenoid valve
2. Injection nozzle
3. De-aerating screw
Fig. C.13: Fuel solenoid valve
C.6.2 Stop solenoid
There are two different variations:
A. Energized to stop
By pressing the „OFF“-button on the remote control panel the stop solenoid is supplied with
voltage and operate, through this the injection nozzles resets to zero position and the generator
stops.
B. Energized to run
This version is equipped with two solenoids an actuating and a stop solenoid. After being fed with
current, the actuating solenoid attracts the adjusting lever of the fuel injection pump, through
which the fuel can flow. The actuating solenoid is switched off once the final position has been
reached, which is maintained by the stop solenoid for as long as the generator is running
.
ATTENTIONT
When starting the "START"-button may not be pressed longer than 5 sec., because the stop sole-
noid pulls too much current over the starter. Otherwise the stop solenoid must be disconnected.
Stop solenoid
Fig. C.14: Stop solenoid
1
2
3