LED INDICATORS

The YZ300 (YZ320) contains 6 LED's that provide information that can be useful in determining the
current state of the interlocks wired between terminals L1 and P of the BurnerLogix control.

Table 2:

YZ300 (YZ320) DEFAULT MESSAGES

STATUS

 – indicates red  when the ED580 co nnection  to th e 

 Bu rnerLogix is interrupted, green when connection is establish ed. 

RECYCLING

 – illuminates steady when  all interlo cks 

 between termin al L1 and 3 are clo sed and powered.  
Blin ks if an y interlock is open. 

WATER

 – illuminates steady when Low Water an d High  

Water are closed  an d powered, blinks  if any  is  open. 

OIL

 – illu minates stead y if all oil interlo cks between 

 terminals 44 and 55 are closed and po wered an d oil is  
an  active fuel, blinks if an y oil in terlock is open. 

GAS

 –  illuminates  steady if  all  gas  interlocks  between   

terminals 50  and 5 4 are clo sed and powered and  gas  is 
 an active fuel, b links if any gas interlock is open. 

NON-RECYCLING

 - illuminates steady when all 

 in terlocks between terminals 54 and  P are closed 
 and powered, blinks if an y interlock is o pen. 

OIL MODE 

GAS  MODE 

Terminal Messa ge  Terminal Message 

Recyc ling Limi ts 

L1-40 

Op Control Open 

L1-40 

Op Control Open 

40-41 

L1-3 Aux#1 Open 

40-41 

L1-3 Aux#1 O pen 

41-42 

L1-3 Aux#2 Open 

41-42 

L1-3 Aux#2 O pen 

42-3 

L1-3 Aux#3 Open 

42-3 

L1-3 Aux#3 O pen 

Non-Recycl ing Limi ts 

3-43 High 

Water 

3-43  High 

Water 

43-44 Low 

Water 

43-44  Low 

Water 

For OIL select, conn ect termi nal 49 to 53 

For GAS  select, conn ect termi nal 45 to 49 

45-46 

High Oi l Temperature 

50-51 

Low Gas Pressure 

46-47 

Low O il Temperature 

51-52 

High Gas Pressure 

47-48 

Low O il  Pressure 

52-53 

Aux G as 

48-49 

Low Atomizing Media 

 

54-55 High 

P re ssure 

54-55  High 

Pressure 

55-56 High 

Temperat ure 

55-56  High 

Temperature 

56-57 

Aux #4 O pen  

56-57 

Aux #4 Open  

57-58 

Aux #5 O pen  

57-58 

Aux #5 Open  

58-59 

Aux #6 O pen  

58-59 

Aux #6 Open  

59-60 

Aux #7 O pen  

59-60 

Aux #7 Open  

60-P 

Air Flow Open 

60-P 

Air Flow Open 

Summary of Contents for YZ300

Page 1: ...rogramming soft ware available from Fireye and the appropriate hardware Note The YZ300 YZ320 Interlock Annunciator does not need to be connected to a BurnerLogix system to be custom programmed Note Pr...

Page 2: ...C EMC Directive 89 336 EEC GASTEC 0063BT1754 EN298 2003 EN230 2005 Table 1 Agency Approvals SPECIFICATIONS Supply Voltage YZ300 120VAC 10 15 50 60 Hz YZ320 230VAC 10 15 50 60 Hz Power Consumption 10 V...

Page 3: ...LOCKOUT 3 P INTLK OPEN to one which will individually identify the sixteen 16 interlocks now being monitored by the YZ300 YZ320 such as LOCKOUT LOW OIL TEM PERATURE or the appropriate modified messag...

Page 4: ...the BurnerLogix control to respond with the proper message Interlock contacts that temporarily open for shorter time periods will be ignored Refer to Figure 2 on page 8 for DEFAULT MESSAGES SPECIAL NO...

Page 5: ...owered and gas is an active fuel blinks if any gas interlock is open NON RECYCLING illuminates steady when all interlocks between terminals 54 and P are closed and powered blinks if any interlock is o...

Page 6: ...et 1000 meters for RS 485 A good ground system should be provided to minimize the effects of AC quality problems A prop erly designed ground system meeting all the safety requirements will ensure that...

Page 7: ...on the underside of the BurnerLogix control Plug end of ED580 cable with ferrite core into EXP port of the BurnerLogix control Plug the other end of the ED580 cable into the EXP port located on the u...

Page 8: ...wn will be undisturbed when the YZ300 YZ320 is installed Remove all power from the BurnerLogix control and the YZ300 YZ320 before wiring Note Terminals 44 45 49 50 and 53 54 are internally connected F...

Page 9: ...es associated with the above terminals can be modified via either the BLL510 or BLV512 displays The selection of available messages are dependent on each group For example the message Low Oil Pressure...

Page 10: ...ning Windows A copy of YZ300P software provided by Fireye An RS232 to RS485 converter serial port required P N EC485 or IC485 includes necessary power supply or USB to RS485 converter P N UC485 An ED5...

Page 11: ...be powered and if not connected to the BurnerLogix the default address is set to 1 and the baud rate is 9600 N 8 1 RUNNING THE YZ300P SOFTWARE 1 Run the YZ300P software on the PC After the introductor...

Page 12: ...ted messages will not be displayed on the YZ300P Write the YZ300P will upload or write all messages to the YZ300 YZ320 If the message displayed on the YZ300P screen is a default message then no writin...

Page 13: ...alled CUSTOMIZING OR ERASING A MESSAGE To customize or erase a message on the YZ300P screen click on the particular message and the fol lowing dialog box will appear The current message pertaining to...

Page 14: ...defective in material or workmanship or which otherwise fails to conform to the description of the prod uct on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE...

Reviews: