2.

A list of available communication baud rates will appear. Use the TAB and arrow keys or mouse
to make the proper selection Press Select to continue.

3.

Assuming the selected COM port is available the following screen appears.

USING THE YZ300P SOFTWARE

Initially, the YZ300P displays the default messages of the YZ300 (YZ320) Interlock Annunciator.
The Command Center allows the user to Read, Write and Erase all stored messages, Open and Save
the message file and select the communication address. Pressing the Quit bar will terminate the pro-
gram.

Read

 - the YZ300P will read all messages currently stored in the YZ300 (YZ320) and display

the custom message in the appropriate location. If no message is stored, the default message will
be displayed. (Library selected messages will not be displayed on the YZ300P).

Write 

- the YZ300P will upload or write all messages to the YZ300 (YZ320). If the message

displayed on the YZ300P screen is a default message then no writing of that message location
will take place.

Erase

 - the YZ300P will send an erase message command to each message location in the

YZ300 (YZ320) and restore that message location to the factory default condition, no message
stored. 

Save

 - the YZ300P allows the current message file to be stored for later recall and re-program-

ming of other YZ300 (YZ320) Interlock Annunciators. Clicking Save will open a dialog box
allowing the user to store the current message file using any descriptive name. The user must
select or create the appropriate folder location to store the file. Typically, the YZ300P wants

During the Read, Write and Erase operations, the progress bar located on the YZ300P
screen will move left to right indicating the status of the selected operation.

Summary of Contents for YZ300

Page 1: ...rogramming soft ware available from Fireye and the appropriate hardware Note The YZ300 YZ320 Interlock Annunciator does not need to be connected to a BurnerLogix system to be custom programmed Note Pr...

Page 2: ...C EMC Directive 89 336 EEC GASTEC 0063BT1754 EN298 2003 EN230 2005 Table 1 Agency Approvals SPECIFICATIONS Supply Voltage YZ300 120VAC 10 15 50 60 Hz YZ320 230VAC 10 15 50 60 Hz Power Consumption 10 V...

Page 3: ...LOCKOUT 3 P INTLK OPEN to one which will individually identify the sixteen 16 interlocks now being monitored by the YZ300 YZ320 such as LOCKOUT LOW OIL TEM PERATURE or the appropriate modified messag...

Page 4: ...the BurnerLogix control to respond with the proper message Interlock contacts that temporarily open for shorter time periods will be ignored Refer to Figure 2 on page 8 for DEFAULT MESSAGES SPECIAL NO...

Page 5: ...owered and gas is an active fuel blinks if any gas interlock is open NON RECYCLING illuminates steady when all interlocks between terminals 54 and P are closed and powered blinks if any interlock is o...

Page 6: ...et 1000 meters for RS 485 A good ground system should be provided to minimize the effects of AC quality problems A prop erly designed ground system meeting all the safety requirements will ensure that...

Page 7: ...on the underside of the BurnerLogix control Plug end of ED580 cable with ferrite core into EXP port of the BurnerLogix control Plug the other end of the ED580 cable into the EXP port located on the u...

Page 8: ...wn will be undisturbed when the YZ300 YZ320 is installed Remove all power from the BurnerLogix control and the YZ300 YZ320 before wiring Note Terminals 44 45 49 50 and 53 54 are internally connected F...

Page 9: ...es associated with the above terminals can be modified via either the BLL510 or BLV512 displays The selection of available messages are dependent on each group For example the message Low Oil Pressure...

Page 10: ...ning Windows A copy of YZ300P software provided by Fireye An RS232 to RS485 converter serial port required P N EC485 or IC485 includes necessary power supply or USB to RS485 converter P N UC485 An ED5...

Page 11: ...be powered and if not connected to the BurnerLogix the default address is set to 1 and the baud rate is 9600 N 8 1 RUNNING THE YZ300P SOFTWARE 1 Run the YZ300P software on the PC After the introductor...

Page 12: ...ted messages will not be displayed on the YZ300P Write the YZ300P will upload or write all messages to the YZ300 YZ320 If the message displayed on the YZ300P screen is a default message then no writin...

Page 13: ...alled CUSTOMIZING OR ERASING A MESSAGE To customize or erase a message on the YZ300P screen click on the particular message and the fol lowing dialog box will appear The current message pertaining to...

Page 14: ...defective in material or workmanship or which otherwise fails to conform to the description of the prod uct on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE...

Reviews: