background image

 

4

a “first out” basis. The first switch which opens in the string to cause the condition will be displayed.
The 3-P circuit is immediately monitored after a burner start-up.

When a “lockout” condition is manually reset, the display on the BurnerLogix and the Interlock
Annunciator Module is ready to begin a new burner sequence. Note the section 

Lockouts 

in the Bul-

letin BL-1001 or BLZ-1001.

Whenever more than one interlock switch in the L1-3 circuit is open on a start-up, the open interlock
switch wired in the sequence closest to the L1 terminal will be displayed. Whenever more than one
interlock switch in the 3-P circuit is open on a startup, the open interlock switch closest to terminal 3
will be displayed.

The YZ300 (YZ320) must be connected to the BurnerLogix control to provide access to the addi-
tional lockout messages associated with the YZ300 (YZ320) Expansion Module.

In operation, the 3 to P and L1 to 3 circuits are checked each half cycle by separate photo optical
couplers in the BurnerLogix system to determine if any interlock is open. Upon detecting an open
interlock, the BurnerLogix control initiates a LOCKOUT or HOLD message, then requests informa-
tion from the YZ300 (YZ320) to determine which interlock corresponding to terminals 43 through
59 and L1 through 42 (on YZ300 [YZ320]) to determine which of the interlocks closest to terminal 3
(3-P circuit) or closest to terminal L1 (L1-3 circuit) is open. The BurnerLogix then selects the corre-
sponding message from the stored message list and displays it. The YZ300 (YZ320) messages then
become a part of the historical data which is stored in the BurnerLogix system memory.

Any interlock in the 3-P or in the L1-3 circuit that opens for at least 33-50 ms while the burner is ON,
or for at least 66 ms while the unit is in PURGE will cause the YZ300 (YZ320) and the BurnerLogix
control to respond with the proper message. Interlock contacts that temporarily open for shorter time
periods will be ignored. Refer to Figure 2 on page 8 for DEFAULT MESSAGES.

SPECIAL NOTES ON OPERATION

After the start of PTFI, if any recycle (L1-3) or running interlock (3-P) limit opens, the BurnerLogix
control will display a POST PURGE message for 15 (or selected post purge time) seconds before
displaying the appropriate message. The appropriate LED located on the face of the YZ300 (YZ320)
will flash to indicate in what section of the circuit the interlock is open.

On recycle type programmers (e.g. YP200 or YP300 set for recycle operation), if a running interlock
(3-P) limit opens, the control will shutdown, perform a post purge and then try to restart. The control
will hold for ten (10) minutes during purge waiting for the limit to close. If a second running inter-
lock opens during this "hold" period, the message may change to reflect the new interlock.

If the operating control limit or auxiliary limit #1, #2 or #3 opens during a firing cycle, the control
will initiate a 15 second post purge and then go to standby and display the message pertaining to the
interlock that opened. The BurnerLogix will wait for all interlocks in the L1-3 circuit to close to
begin a new cycle.

If multiple interlocks in the 3-P circuit are opened during the start of a burner cycle, the first inter-
lock in the following sequence will be displayed.

CAUTION: The YZ300 (YZ320) messages are stored within the Interlock Annunciator
Module. The YZ300 (YZ320) messages shown in Table 2 on page 5, and on the wiring dia-
gram, Figure 2 on page 8, represent the default messages that are shipped with each Inter-
lock Annunciator module. Unless these default messages are modified via the BLL510 or
BLV512 display module or customized via a PC (Refer to CUSTOMIZING YZ300
(YZ320) MESSAGES in this bulletin), the YZ300 (YZ320) must be wired EXACTLY AS
SHOWN, in the sequence as shown in the wiring diagram, Figure 2 on page 8, to ensure
proper operation.

Summary of Contents for YZ300

Page 1: ...rogramming soft ware available from Fireye and the appropriate hardware Note The YZ300 YZ320 Interlock Annunciator does not need to be connected to a BurnerLogix system to be custom programmed Note Pr...

Page 2: ...C EMC Directive 89 336 EEC GASTEC 0063BT1754 EN298 2003 EN230 2005 Table 1 Agency Approvals SPECIFICATIONS Supply Voltage YZ300 120VAC 10 15 50 60 Hz YZ320 230VAC 10 15 50 60 Hz Power Consumption 10 V...

Page 3: ...LOCKOUT 3 P INTLK OPEN to one which will individually identify the sixteen 16 interlocks now being monitored by the YZ300 YZ320 such as LOCKOUT LOW OIL TEM PERATURE or the appropriate modified messag...

Page 4: ...the BurnerLogix control to respond with the proper message Interlock contacts that temporarily open for shorter time periods will be ignored Refer to Figure 2 on page 8 for DEFAULT MESSAGES SPECIAL NO...

Page 5: ...owered and gas is an active fuel blinks if any gas interlock is open NON RECYCLING illuminates steady when all interlocks between terminals 54 and P are closed and powered blinks if any interlock is o...

Page 6: ...et 1000 meters for RS 485 A good ground system should be provided to minimize the effects of AC quality problems A prop erly designed ground system meeting all the safety requirements will ensure that...

Page 7: ...on the underside of the BurnerLogix control Plug end of ED580 cable with ferrite core into EXP port of the BurnerLogix control Plug the other end of the ED580 cable into the EXP port located on the u...

Page 8: ...wn will be undisturbed when the YZ300 YZ320 is installed Remove all power from the BurnerLogix control and the YZ300 YZ320 before wiring Note Terminals 44 45 49 50 and 53 54 are internally connected F...

Page 9: ...es associated with the above terminals can be modified via either the BLL510 or BLV512 displays The selection of available messages are dependent on each group For example the message Low Oil Pressure...

Page 10: ...ning Windows A copy of YZ300P software provided by Fireye An RS232 to RS485 converter serial port required P N EC485 or IC485 includes necessary power supply or USB to RS485 converter P N UC485 An ED5...

Page 11: ...be powered and if not connected to the BurnerLogix the default address is set to 1 and the baud rate is 9600 N 8 1 RUNNING THE YZ300P SOFTWARE 1 Run the YZ300P software on the PC After the introductor...

Page 12: ...ted messages will not be displayed on the YZ300P Write the YZ300P will upload or write all messages to the YZ300 YZ320 If the message displayed on the YZ300P screen is a default message then no writin...

Page 13: ...alled CUSTOMIZING OR ERASING A MESSAGE To customize or erase a message on the YZ300P screen click on the particular message and the fol lowing dialog box will appear The current message pertaining to...

Page 14: ...defective in material or workmanship or which otherwise fails to conform to the description of the prod uct on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE...

Reviews: