3
FIGURE 1.
DIMENSIONS
The location should be free from excessive vibration and within the ambient temperature rating.
ORDERING INFORMATION
OPERATION
The YZ300 (YZ320) Interlock Annunciator Module is designed to expand the capability of the
BurnerLogix System by allowing the operator to individually track the operation of four (4) recy-
cling interlocks and sixteen (16) running interlocks (non-recycling). The recycling interlocks are
wired between the L1-3 terminals on the BurnerLogix wiring base and the non-recycling interlocks
are in the 3-P circuit.
Referring to the wiring diagram, Figure 2 on page 8, the operating control and auxiliary limits 1, 2
and 3 will act as an operating control to recycle the burner. Whenever any of the auxiliary limits are
open and the other limits are closed, the message on the display of the BurnerLogix control will indi-
cate:
STANDBY
L1-3 AUX #1(or #2, or #3) OPEN (or the appropriate modified message)
Similarly, the interlocks in the 3-P circuit will change the standard running interlock message on the
display from: LOCKOUT 3-P INTLK OPEN to one which will individually identify the sixteen (16)
interlocks now being monitored by the YZ300 (YZ320), such as, LOCKOUT LOW OIL TEM-
PERATURE (or the appropriate modified message). The interlock switch chosen will be selected on
Part Number
Description
YZ300
Interlock Annunciator Module used with the YB110 or ZB110 BurnerLogix chassis/amplifier,
120 VAC, +10%, -15%, 50/60 Hz
YZ320
Interlock Annunciator Module used with the YB230 or ZB230 BurnerLogix chassis/amplifier,
230 VAC, +10%, -15%, 50/60 Hz
60-2872-1
Wiring base, terminal blocks, closed with knockouts
60-2874-1
Wiring base, terminal blocks, open end
ED580-2, -4, -8
YB110 or ZB110 to YZ300 interconnection cable in 2’, 4' and 8' lengths
YZ300P
Windows based software for programming custom messages.
Download from http://www.fireye.com/Documents/YZ300P.zip
EC485
RS232 to RS485 converter with power supply. Required to customize YZ300 messages
UC485
USB to RS485 converter with USB cable. Required to customize YZ300 messages
ED512-2, 4, -8
Cable with RJ12 connectors on each end. Required to customize YZ300 lockout alarm messages
INTERLOCK
ANNUNCIATOR
STATUS
RECYCLING (L1 - 3)
WATER (3 - 44)
OIL (44 - 50)
GAS (50 - 54)
NON-RECYCLING (54 - P)
Height with control installed is 5.8 " (147mm)
4.0”
(101mm)
(127mm)
5.0”