The location should be free from excessive vibration and within the ambient temperature rating.

ORDERING INFORMATION

OPERATION

The YZ300 (YZ320) Interlock Annunciator Module is designed to expand the capability of the
BurnerLogix System by allowing the operator to individually track the operation of four (4) recy-
cling interlocks and sixteen (16) running interlocks (non-recycling). The recycling interlocks are
wired between the L1-3 terminals on the BurnerLogix wiring base and the non-recycling interlocks
are in the 3-P circuit.

Referring to the wiring diagram, Figure 2 on page 8, the operating control and auxiliary limits 1, 2
and 3 will act as an operating control to recycle the burner. Whenever any of the auxiliary limits are
open and the other limits are closed, the message on the display of the BurnerLogix control will indi-
cate:

STANDBY

L1-3 AUX #1(or #2, or #3) OPEN (or the appropriate modified message)

Similarly, the interlocks in the 3-P circuit will change the standard running interlock message on the
display from: LOCKOUT 3-P INTLK OPEN to one which will individually identify the sixteen (16)
interlocks now being monitored by the YZ300 (YZ320), such as, LOCKOUT LOW OIL TEM-
PERATURE (or the appropriate modified message). The interlock switch chosen will be selected on

Part Number

Description

YZ300

Interlock Annunciator Module used with the YB110 or ZB110 BurnerLogix chassis/amplifier, 
120 VAC, +10%, -15%, 50/60 Hz

YZ320

Interlock Annunciator Module used with the YB230 or ZB230 BurnerLogix chassis/amplifier, 
230 VAC, +10%, -15%, 50/60 Hz

60-2872-1

Wiring base, terminal blocks, closed with knockouts

60-2874-1

Wiring base, terminal blocks, open end

ED580-2, -4, -8

YB110 or ZB110 to YZ300 interconnection cable in 2’, 4' and 8' lengths

YZ300P

Windows based software for programming custom messages. 
Download from http://www.fireye.com/Documents/YZ300P.zip

EC485

RS232 to RS485 converter with power supply. Required to customize YZ300 messages

UC485

USB to RS485 converter with USB cable. Required to customize YZ300 messages

ED512-2, 4, -8

Cable with RJ12 connectors on each end. Required to customize YZ300 lockout alarm messages

 

INTERLOCK

ANNUNCIATOR

STATUS

RECYCLING (L1 - 3)

WATER (3 - 44)

OIL (44 - 50)

GAS (50 - 54)

NON-RECYCLING (54 - P)

Height with control installed is 5.8 " (147mm)

4.0”

(101mm)

(127mm)

5.0”

Summary of Contents for YZ300

Page 1: ...rogramming soft ware available from Fireye and the appropriate hardware Note The YZ300 YZ320 Interlock Annunciator does not need to be connected to a BurnerLogix system to be custom programmed Note Pr...

Page 2: ...C EMC Directive 89 336 EEC GASTEC 0063BT1754 EN298 2003 EN230 2005 Table 1 Agency Approvals SPECIFICATIONS Supply Voltage YZ300 120VAC 10 15 50 60 Hz YZ320 230VAC 10 15 50 60 Hz Power Consumption 10 V...

Page 3: ...LOCKOUT 3 P INTLK OPEN to one which will individually identify the sixteen 16 interlocks now being monitored by the YZ300 YZ320 such as LOCKOUT LOW OIL TEM PERATURE or the appropriate modified messag...

Page 4: ...the BurnerLogix control to respond with the proper message Interlock contacts that temporarily open for shorter time periods will be ignored Refer to Figure 2 on page 8 for DEFAULT MESSAGES SPECIAL NO...

Page 5: ...owered and gas is an active fuel blinks if any gas interlock is open NON RECYCLING illuminates steady when all interlocks between terminals 54 and P are closed and powered blinks if any interlock is o...

Page 6: ...et 1000 meters for RS 485 A good ground system should be provided to minimize the effects of AC quality problems A prop erly designed ground system meeting all the safety requirements will ensure that...

Page 7: ...on the underside of the BurnerLogix control Plug end of ED580 cable with ferrite core into EXP port of the BurnerLogix control Plug the other end of the ED580 cable into the EXP port located on the u...

Page 8: ...wn will be undisturbed when the YZ300 YZ320 is installed Remove all power from the BurnerLogix control and the YZ300 YZ320 before wiring Note Terminals 44 45 49 50 and 53 54 are internally connected F...

Page 9: ...es associated with the above terminals can be modified via either the BLL510 or BLV512 displays The selection of available messages are dependent on each group For example the message Low Oil Pressure...

Page 10: ...ning Windows A copy of YZ300P software provided by Fireye An RS232 to RS485 converter serial port required P N EC485 or IC485 includes necessary power supply or USB to RS485 converter P N UC485 An ED5...

Page 11: ...be powered and if not connected to the BurnerLogix the default address is set to 1 and the baud rate is 9600 N 8 1 RUNNING THE YZ300P SOFTWARE 1 Run the YZ300P software on the PC After the introductor...

Page 12: ...ted messages will not be displayed on the YZ300P Write the YZ300P will upload or write all messages to the YZ300 YZ320 If the message displayed on the YZ300P screen is a default message then no writin...

Page 13: ...alled CUSTOMIZING OR ERASING A MESSAGE To customize or erase a message on the YZ300P screen click on the particular message and the fol lowing dialog box will appear The current message pertaining to...

Page 14: ...defective in material or workmanship or which otherwise fails to conform to the description of the prod uct on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE...

Reviews: