3
The igniter function is activated with a 24 VDC triggering signal from the burner management system
(terminals 3, 4 on Fig. 4 and 5). Once energized, the green "IGNITION" indication LED on the enclosure door
will light. The 24VDC control signal from the Burner Management System operates an internal relay which
powers the HV ignition transformer, which in turn creates an 8,000 VAC spark at the igniter tip.
In case another triggering voltage is needed contact Fireye.
After the Trial for Ignition, the control signal is switched off, the relay changes state to allow ionization
detection to indicate presence of flame.
This signal from the ionization rod is connected to
MBCE-110/230FR
flame sensor module in
HTSS-PP
or
HTSS-PP-CEX
power packs, which provides an isolated Flame Relay signal.
The
MBCE
module, also provides a 4-20 mA signal to display flame intensity (see the Fireye Instruction
Manual no
MBCE-1001
). Be aware that for proper ionization measurement a pilot body should be properly
constructed and connected (grounded) to the ionization circuit terminals in power pack (see Fig. 4 or 5).
FIGURE 2.
High Tension Igniter type HTSS including rod, HV cable and Power Pack for ignition and Spark & Sense as an option,
for Safe or Hazardous Areas.
Safe Area
HV single wire cable 5 m
L1
Exchangeable rod tip, short, P/N
HTR-TIP
~ 145 mm
~ 160 mm
~ 50 mm
Power Pack, P/N
HTSS-PP-230
or
HTSS-PP-110
including power board with:
HV transformer, MBCE-FR module base, ignition relay, Spark & Sense circuit
in Carbon Steel painted or Stainless Steel cabinet with one gland and mounting lugs,
IP66, LxWxD 250x200x150
Igniter rod P/N
HTSS-xxx-J
, with junction box IP67, replaceable tip,
includes separate 5 m HV cable. For use in safe zone only
POWER ON
IGNITION
O 9
7
O 13
Mounting lug
3
10 mm
Ignition rod nameplate, 45x15 mm
Igniter nameplate
127x57 mm
Cable gland
~ 460 mm
Exchangeable rod tip, long, P/N
HTR-TIP-L
~ 40 mm
~ 60 mm
160 mm
Hazardous Area
L1
~ 145 mm
L1
~ 345 mm
~ 50 mm
~ 50 mm
Power Pack P/N
HTSS-PP-230-CEX
or
HTSS-PP-110-CEX
, including power board with:
HV transformer, MBCE-FR module base, ignition relay, Spark & Sense circuit,
in Exd cast Aluminium Alloy epoxy painted or S.S. enclosure type GUB4 with Exd HV
cable gland and stop plugs. For use in hazardous Zone 1.
IP66, O.D. LxWxD 309x281x225 mm.
Igniter rod P/N
HTSS-xxx-CEX
with replaceable tip (short or long),
IP66, integral 5 m HV cable. For use in hazardous Zone 1.
HV shielded single wire cable
Igniter rod P/N
HTSS-xxx-J-CEX
with Exd junction box IP66, replaceable tip
(short or long), includes separate HV shielded cable, length 5 m.
For use in hazardous zone 1.
313 mm
281 mm
2 x O 12 mm
GUB 4
Igniter
nameplate
127x57 mm
Rod nameplate and ATEX plate, 45x15 mm each
Rod nameplate 45x15 mm
Rod ATEX plate 45x15 mm
GUB4
ATEX plate
127x57 mm
Exd gland
Exd stop plug