15
8.6 If there is no flame confirmation on flame safeguard module and the rod is in correct position in gas igniter and
also flame is present there, perform the steps as in p. 8.1 a) to e), in particular perform measurements and check
connections of a pilot body to the ionization circuit (see Fig 3 or 4, 5).
Try to identify and replace faulty part by performing the steps as above. If still there is no flame confirmation
replace the
MBCE
module.
8.7 For any services and troubleshooting of
MBCE-FR
module refer to Fireye Bulletin No
MBCE-1001
.
8.8 For any services and troubleshooting of
SP-32-
NG/PG-FD
,
SP-32-NG/PG-ND
,
SP-48-NG/PG-ND
or
SP-48-NG/PG-FD
gas pilot refer to Fireye Bulletins No
S
F-200
,
SF-300
,
SF-500
or
SF-600
.
8.9 If, after all above measures have been taken, the
HTSS
igniter does not work properly, contact the
manufacturer's service department.
8.10 Before any changes in igniter circuit, replacing components always disconnect the supply.
8.11 Before performing any functional tests connect the grounding and only then connect supply.
9. SPARE PARTS, WARRANTY CONDITIONS
9.1 Igniter operation-consumable
parts and suggested spare parts quantity:
- Rod Tip, short or long
P/N
HTR-TIP
or
HTR-TIP-L
- one for 4 igniters,
- Rod Tip Long rear ceramic sleeve - 2 pcs
P/N
HTR-TIP-L-CER
- one for 8 igniters,
- HV transformer 230VAC/8000VAC
P/N
TX-230-8000
- one for 8 igniters,
- HV transformer 110VAC/8000VAC
P/N
TX-110-8000
- one for 8 igniters,
- Ignition relay 24VDC/12 A
P/N
HT-REL-24
- one for 8 igniters,
- HV cable, 5 m long
P/N
HT-CAB-5
or
-CEX
- one for 8 igniters.
Complete list of igniter spare parts Part Numbers is in Table 5
.
9.2
HTSS
construction includes two types of wearing parts:
Rod Tips, short and long P/N
HTR-TIP
and
HTR-TIP-L
- their lifetime is 200,000 arc cycles
ATTENTION:
Above lifetime refers to laboratory test conditions.
In the real combustion chamber environment, these values are lower. Operation in high temperature
conditions, corrosive properties of fuel, impacts and mechanical damages, residues and slag on the tip - can
significantly reduce the tip's life.
9.3
The warranty (see page 20) does not apply to ignition rod tips P/N
HTR-TIP
or
HTR-TIP-L as their life
time depend on the quantity of ignition cycles and the conditions they have to work under.
Each rod tip has one month warranty to be checked on receipt or within 1 month, for damage and tested for the
proper functioning. Fireye should be notified of any failure. After 1 month, the warranty on tip expires.
9.4
This guarantee covers delivered devices and materials under conditions of proper installation, start-up,
operation and maintenance, it means the use in accordance with applicable instructions and manuals.
This is particularly applicable to overheated parts i.e. working above their maximum operating
temperature defined in Instruction Manual.
9.5 The defective device or part will be replaced or repaired at manufacturer’s option.
The warranty applies to and may be executed only on a failed device send to the manufacturer warehouse for
examination or warranty repair.
9.6 The manufacturer does not accept liability for damage to persons or property resulting from:
–
mechanical damages, overheating
–
improper installation, operation, maintenance of igniter contrary to the instructions in the user manual,
–
unauthorized igniter modifications or repairs made by unauthorized personnel,
–
use of components or spare parts other than original.
9.7 During the guarantee period any repairs must
be carried out by the manufacturer service department, or the user,
upon the service's notification and consent.
9.8 Replacement of the consumables can be user-performed only after expiration of the guarantee.