Supply voltage 230/110VAC has to be connected to power pack terminal. The ignition is activated with
a 24 VDC triggering signal (see below). Lack of
MBCE
module does not affect the ignition sequence.
FIGURE 1.
High Tension Igniter type HTSS including rod, HV cable and ignition transformer for Safe or Hazardous Areas.
Operation as a “Spark & Sense” igniter:
HTSS can be used as a “Spark & Sense” igniter i.e. as igniter with additional flame safeguard operation
mode based on the principle of measuring of the ionization current in electrically conductive ionized gas in
a flame. This flame detection method used in HTSS is called ionization (rectification) method.
In such case the scope is:
one of High Tension Rods
P/N:
HTSS-xxx-J
,
HTSS-xxx-CEX
or
HTSS-xxx-J-CEX
(each including HV cable) and
Power Pack
P/N:
HTSS-PP-230/110
or
HTSS-PP-230/110-
CEX
including Fireye
MBCE-110/230FR flame module
plugged in the wiring base (order separately) ((see
Fig. 2 or 4, 5 for Safe or Hazardous Area).
In both operation modes the
HTSS
power pack must be permanently powered with 230/110VAC which is
confirmed by "POWER ON" red indication LED on the enclosure door.
HV single wire cable 5 m
L1
Igniter rod P/N
HTSS-xxx-J
,
includes:
replaceable tip (see Fig. 2), separate
5 m HV cable.
L N PE
Power Supply
110/230 VAC
HV Ignition Transformer
P/N
TX-230/110-8000
LxWxD 107x87x64
grounding wire - by others
GREEN / YELLOW
REMARK:
Enclosure with terminal, mounting parts,
supports, glands, wiring - by others
Safe Area
High Tension
8000V outputs
mounting holes 2 x O 5.2 mm,
4 x O 4.2 mm
L1
Igniter rod P/N
HTSS-xxx-CEX
with
integral 5 m HV cable, includes
replaceable tip (see Fig. 2).
L N PE
Power Supply
110/230 VAC
HV shielded single wire cable
REMARK:
ATEX Exd enclosure with terminal, mounting parts,
supports, glands, wiring - by others
HV Ignition Transformer
P/N
TX-230/110-8000
LxWxD 107x87x64
REMARK:
Shield of HV cable connect to a drain wire and then to
HV Ignition Transformer output - by others
L1
Igniter rod P/N
HTSS-xxx-J-CEX
includes: replaceable tip
(see Fig. 2), separate HV shielded cable, length 5 m.
Hazardous Area
Protective ground
High Tension
8000V outputs
mounting holes 2 x O 5.2 mm,
4 x O 4.2 mm