The “Check-Run” switch has been placed in the Check position with the operating
control circuit (L1-13) open. Every time the Reset button is depressed and held for
one second will increment the Unit Address by one. Refer to programmer bulletin
for additional information on Unit Address.
DIAGNOSTIC MESSAGES
POSSIBLE CAUSE
SOLUTION
— High electrical noise
— Check for proper ground on power supply.
— Install noise suppressor on power supply.
— Defective field wiring.
— Make sure line phase on interlock circuit is
the same as found on L1/L2 power supply to
E110.
— Defective amplifier.
— Replace amplifier.
— Defective IR scanner.
— Replace IR cell.
— Voltage on terminal 7 at
improper time.
— Defective Chassis.
— Defective Programmer.
— Check wiring to terminal 7.
— Replace Chassis (EB700).
— Replace Programmer.
— Voltage on terminal 5 or 6 at improper
time.
— High Electrical Noise.
— Failed Programmer.
— Worn Chassis.
— Check wiring to terminals 5 and 6.
— Install noise suppressor on power
supply
— Re-route scanner wires away from high
voltage wiring.
— Replace Programmer.
— Replace Chassis.
— Flame signal detected during shutter
close time on 45UV5 scanner.
— Stuck scanner shutter. Replace 45UV5
scanner.
— The E300 Expansion Module has a
defective optocoupler.
— Replace E300 Expansion Module.
— Amplifier has failed diagnostic checks.
— Replace amplifier.
— Defective programmer.
— Replace programmer.
CHECK STANDBY
00
UNIT ADDRESS
LOCKOUT AUTO
CHECK AMPLIFIER
LOCKOUT PTFI
CHECK CHASSIS
LOCKOUT PURGE
CHECK PROGRAMMER
LOCKOUT AUTO
CHECK SCANNER
LOCKOUT AUTO
CHECK EXPANSION MODULE
LOCKOUT AUTO
AUTO CHECK AMPLIFIER FAIL
FIREYE ED510
SYSTEM ERROR