23
®
TO MODIFY THE E300 MESSAGES
All three keys: Mode, Reset and Scroll, are used to modify the E300 messages. The Mode key is
used to enter or exit the sub-menu associated with the E300 messages. The Scroll key is used to
advance through the various terminals or selectable messages. The Reset key is used to modify a ter-
minal message and select a new message. To modify the E300 messages:
Press the Scroll key until the ED510 displays
E300 MSG SELECT.
Press the Mode key and the screen displays:
E300 TERM #20-21
L1-13 AUX#1 OPEN
or programmed message.
Press the Scroll key and the screen displays:
E300 TERM #21-22
L1-13 AUX#2 OPEN
or programmed message.
To change the message, press and hold the Reset key for one (1) second. When the Reset key is
released, the screen displays:
MDFY TERM #21-22
L1-13 AUX#2 OPEN
Press the Scroll key to display the available messages for the particular group being modified. See
attached List of available messages for each group.
When the messages displayed is appropriate for the terminals, press and hold the Reset key for one
(1) second. When the Reset key is released, the screen displays:
E300 TERM #21-22
LOW WATER
or programmed message.
Press the Mode key to exit the E300 Message Sub-menu.
AVAILABLE E300 MESSAGES
The following messages are available for each of the four E300 terminal groups:
GROUP 1 — RECYCLE
E340 OP CNTL OPEN
HIGH WATER
CONTROL PANEL SWITCH OPEN
DAMPER POSITION END SWITCH
OPEN
BLOWER MOTOR INTLK
HIGH GAS PRESSURE
COMBUSTION AIR END SWITCH OPEN
HIGH STACK TEMPERATURE
LOW GAS PRESSURE
LOW WATER
GROUP 2 — OIL SELECT
LOW OIL PRESSURE
LOW OIL TEMPERATURE
LOW ATOMIZING MEDIA
HIGH OIL PRESSURE
HIGH OIL TEMPERATURE
GROUP 3 — GAS SELECT
HIGH GAS PRESSURE
LOW GAS PRESSURE
GROUP 4 — NON-RECYCLE
E340 SAFETY INTLK OPEN
HIGH TEMPERATURE
BLOWER MOTOR INTLK
HIGH WATER
AIR FLOW OPEN
I.D. FAN INTLK
LOW WATER
OIL GUN END SWITCH OPEN
F.D. FAN INTLK
HIGH PRESSURE
HIGH STACK TEMPERATURE