9
®
PROGRAMMER AND DISPLAY MODULE COMPATIBILITY
All programmers for the Flame-Monitor Series are designated with the prefix “EP” or “EPD.” The
ED510 is a 2 line by 16 character LCD display with keypad to provide both current and historical
information pertaining to the operation of the control. Refer to Bulletin ED-5101 for a complete
description of the features and capabilities of the ED510 display module. The ED500 is an eight
character LED display, was the predecessor to the ED510 and does not have the latest features of the
ED510 display module. EP style programmers with an Engineering code of 28 or later (e.g. 9414-28)
are compatible with both the ED510 and ED500 display module. EP style programmers with an
Engineering code before 28 are only compatible with the ED500 display. The EPD style program-
mers (with an Engineering code 02 or later) are compatible with the ED510 display module as well.
Note: The EPD style programmers do not require a display module to function.
FIREYE
PART
NUMBER
Pre-purge
program-
ming
(Seconds)
Proven
High Fire
Purge
Interlock
(D/8 Ckt)
Proven
Low Fire
Start
Interlock
(M/D Ckt)
Intermittent
Ignition/
Pilot
Interrupted
Ignition/
Pilot
Early Spark
Termination
Pilot
Trial-for-Ignition
Main
Trial-for-Ignition
Running
Interlock
(3/P CKT)
Firing Rate
Motor
Circuit
EPD/EP
2
PROGRAMMERS
EPD160
EP160
EPD167
8
30
1
Supervised
Yes
Yes
No
Yes
No
10
10
10
15
Non Recycle
Yes
EPD161
EP161
30
1
Supervised
Yes
Yes
No
Yes
No
10
10
10
30
Non Recycle
Yes
EP165
7
30
1
Supervised
Yes
Yes
No
Yes
No
10
10
—
10
6
Non Recycle
Yes
EP166
7
30
1
Supervised
Yes
Yes
No
Yes
No
10
10
—
15
6
Non Recycle
Yes
EPD170
EP170
30
1
Supervised
Yes
Yes
No
Yes
Yes
5
10
—
10
Non Recycle
Yes
EPD260
EP260
30
1
No
Yes
No
Yes
No
10
10
10
15
Recycle
Yes
EPD261
30
1
No
Yes
No
Yes
No
10
10
10
30
Recycle
Yes
EPD270
EP270
30
1
No
Yes
No
Yes
Yes
5
10
—
10
Recycle
Yes
EPD380
EP380
EP387
8
30
No
Yes
Yes
3
Yes
Yes
4
10
10
10
Intermittent
3
Recycle
5
None
EPD381
EP381
15
No
Yes
Yes
3
Yes
Yes
4
10
10
10
Intermittent
3
Recycle
5
None
EPD382
EP382
0 No
Yes
Yes
3
Yes
Yes
4
10
10
10
Intermittent
3
Recycle
5
None
EPD390
EP390
90
No
Yes
Yes
3
Yes
Yes
4
10
10
10
Intermittent
3
Recycle
5
None
All programmers have a maximum 4 second Flame Failure Response Time (FFRT) with the exception of the EP165 and EP166 (2 sec. FFRT).
All EPD Programmers and EP Programmers have selectable 3-P Proven Open to Start feature via dipswitch.
1
These programmers add a 30 second waiting period to the prepurge while the firing rate motor is driven to the low fire position.
2
Purge timings can be extended via dipswitches of EP style programmers.
3
Selectable intermittent or interrupted (15 sec. MTFI) operation of terminal 6 via dipswitch (EP models only).
4
These programmers can use terminal “X” for spark termination. This requires jumpering terminals 5 and 10 on the wiring base. PTFI timing is 5 seconds on terminal “X.”
5
Selectable Recycle or Non-Recycle Operation via dipswitch.
6
During MTFI terminal 6 is energized for 5 seconds (pilot stabilization) before energizing terminal 7 for 10 seconds for EP165 and 15 seconds for EP166 only.
7
EP165 will lockout on power interruption.
8
The EPD167 and EP387 wait indefinitely for the low fire start switch (M-D) to close.
Term 5
Term 6
Term 5
Term 6