FLAME-MONITOR SPECIFICATIONS
Supply Voltage:
E110:
120 VAC (+10%, -15%) 50/60 Hz
E120:
220 VAC (+10%, -15%) 50/60 Hz
Power Consumption:
25 VA
Shipping Weight:
(E110 Approx.) 5 lbs. (2.3kg)
OPERATING TEMPERATURE LIMITS
LOAD RATINGS
Maximum Simultaneous Connected Load:
2000 VA
CONTROL
MAXIMUM
MINIMUM
E110, E120, EB700, EB701
140°F
60°C
- 40°F
- 40°C
EP, EPD Programmers
140°F
60°C
- 40°F
- 40°C
All Amplifiers
140°F
60°C
- 40°F
- 40°C
ED510 Display
140°F
60°C
32°F
0°C
Scanner UV1A, UV2, UV8A,
45UV3, UV90
200°F
93°C
- 40°F
- 40°C
45UV5-1007, 45UV5-1009
200°F
93°C
- 40°F
- 40°C
Flame Rod
(Tip 2460 F)
1500°F
816°C
- 40°F
- 40°C
48PT2
140°F
60°C
- 40°F
- 40°C
Humidity: 85% R.H. (Non-condensing)
TERMINAL
TYPICAL LOAD
A. Maximum Rating @120V-50/60Hz
B.
Alternate Rating @120-50/60Hz
5, 6 Individually or
Combined
Pilot Valve(s) and Igni-
tion Transformer(s)
50VA Pilot Duty (Solenoid Valves)
plus 500VA (Transformer)
125VA Pilot Duty Solenoid Valves plus
250VA (Transformer)
7
Main Fuel Valve(s)
250VA Pilot Duty (Solenoid Valve)
1250 VA Opening 500 VA Holding
(Motorized Valve) plus 65 VA Pilot Duty
(Solenoid Valve)
M
Burner/Blower Motor
9.8 F.L.A. * 58.8 L.R.A.
240 VA Pilot Duty (Motor Starter Coil)
10-11-12-X
Modulator
125 VA Pilot Duty
A
Alarm
50 VA Pilot Duty
Terminal ratings may be selected from either column A or B: (select the rating from the column for each terminal which best applies to
the connected load on that terminal).
* F.L.A. = full load amps L.R.A. = locked rotor amps
CAUTION: While programmers are mechanically interchangeable in that they mate with
a common wiring base, you should select the correct model for your application. Inappro-
priate application of a control could result in an unsafe condition hazardous to life and
property. Selection of a control for a particular application should be made by a competent
professional, such as a boiler/burner service technician licensed by a state or other govern-
ment agency.