18
Installation
(for qualified installers only)
Travis Industries
9 3 5 0 8 1 1 6
0 3 1 0 0 0
Approved Vent Configurations
Restrictor Position
•
A vent and intake restrictor is built into the appliance to adjust the flow rate of exhaust gases.
Depending upon the vent configuration, you may be required to adjust the restrictor position. The
charts for acceptable vent configurations detail the correct vent restrictor position.
TO CHANGE THE RESTRICTOR (both intake & vent restrictor must be set to the correct position):
1) Remove the baffle
2) Remove the two screws holding the vent restrictor plate.
3) Move the vent restrictor plate so the correct hole lines up with the holes in the back of the firebox.
4) Replace the two screws. Replace the baffle.
5) Remove the two screws holding the intake restrictor plate.
6) Move the intake restrictor plate so the correct hole lines up with the holes in the back of the firebox.
7) Replace the two screws.
5/16" Nutdriver
VENT RESTRICTOR
The restrictor is shipped
like this (position # 1).
1/4" Nutdriver
Position # 10
etc...
Position # 3
Position # 2
This restrictor is in
position # 4.
INTAKE RESTRICTOR
Baffle
(remove to access the vent restrictor)
1/4" Nutdriver
The restrictor is shipped
like this (position # 1).
Position # 10
etc...
Position # 3
Position # 2
This restrictor is in
position # 4.
Elbows
•
See the vent
configurations for
details on how
many elbows may
be used and in
what manner.
Measuring Vent
Lengths
Vent
Horizontal
Run
Vent
Height
30-7/8"
Vent Height is calculated to
the top of the vent on
horizontal terminations and
to the top of the termination
on vertical terminations.
Elbows add 3" to
the length of the
vent system.
Side
View
9-5/8"
3"
1-1/2"
Vent Length
(3', 4', etc.)
Vent sections overlap each
other by 1-1/2"
1-1/2"
8-3/4" wide with
1-1/2" to 3-3/8" of
overlap
12-3/8" tall with 1-
1/2" of overlap