9
TECHNICAL SPECIFICATION
26
9-C: RDB 2.2 Range Burner Settings (D).
The above performance figures are based on ideal laboratory test conditions.
Air shutter settings above may need to be revised to take into consideration
difference in resistances between conventional and balanced flue installations.
Use flue gas analyser to achieve optimum results.
Variations in nozzle throughput, flue type & draught, oil viscosity etc. may
give results differing from these laboratory performance figures.
DIESEL SETTINGS
for Firebird Boiler Range Using RDB 2.2 Burner
Output
Range
Nozzle
Pump
Head
Air
CO2
Air
Btu
Size-Type
Pressure bar
Type
Box
70,000
70,000
0.50 80˚H
12.0 bar
T1
2.0
12%
1
90,000
75,000
0.50 80˚H
13.5 bar
T3
2.0
12%
1
90,000
80,000
0.55 80˚S
12.0 bar
T3
2.2
12%
1
90,000
90,000
0.55 80˚S
13.5 bar
T3
2.8
12%
1
120,000
110,000
0.65 80˚S
12.5 bar
T5
2.4
12%
2
120,000
120,000
0.65 80˚S
12.3 bar
T5
3.0
12%
2
150,000
142,000
0.85 80˚S
13.0 bar
T5
4.0
12%
2