Programming for DACT-UD
Programming the MS-9600 Fire Alarm Control Panel
34
DACT-UD PN 51899:B1 1/25/05
Report Style
Pressing
3
while viewing Central Station Screen #2 will cause the Report Style
display to toggle between
Point
and
Zone
. Setting the Report Style to Point will
program the DACT to report individual point status to the Central Station. The
control panel is capable of monitoring a total of 636 addressable devices. Setting
the Report Style to Zone will program the DACT to report zone status to the Central
Station. The control panel is capable of monitoring a total of 99 individual zones.
Notes on Central Station Reporting:
1.
SLC Loop 1
, Detector Address 01 will be reported to the Central Station as
Point 01, Detector Address 02 as Point 02, with reports continuing in a similar
fashion all the way up to Detector Address 159 which will be reported as Point
159.
2.
SLC Loop 1
, Module Address 01 will be reported to the Central Station as
Point 160, Module Address 02 will be reported to the Central Station as Point
161, with reports continuing in a similar fashion all the way up to Module
Address 159 which will be reported as Point 318.
3.
SLC Loop 2
, Detector Address 01 will be reported to the Central Station as
Point 319, Detector Address 02 as Point 320, with reports continuing in a
similar fashion all the way up to Detector Address 159 which will be reported
as Point 477.
4.
SLC Loop 2
, Module Address 01 will be reported to the Central Station as
Point 478, Module Address 02 as Point 479, with reports continuing in a
similar fashion all the way up to Module Address 159 which will be reported as
Point 636.
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE POINT
Central Station Screen #2