Programming the MS-9600 Fire Alarm Control Panel
Programming for DACT-UD
DACT-UD PN 51899:B1 1/25/05
21
3.1.1.4.3 Ring Count
The ring count designates the number of rings allowed on the phone line prior to
answering an incoming call from a service terminal. The factory default is
3
which
means the control panel will not answer an incoming call until 3 rings are detected.
This entry may be programmed for
1
to
25
rings. A setting of
00
prevents the panel
from answering incoming calls.
To change the Ring Count, press
1
while viewing the Service Terminal Screen #2.
The following screen will be displayed:
A flashing cursor will appear in the lower left corner of the display. Enter the two-
digit ring count which can be a value between 00 and 25. After the second digit is
entered, the display will return to the Service Terminal screen.
3.1.1.5 Central Station
Central Station programming configures the control panel DACT for contacting the
central station. Pressing
2
while viewing On Board DACT Screen #2 will cause the
following screens to be displayed:
3.1.1.5.1 Reporting Enable
To enable the DACT for reporting FACP activity to the central station, press
1
while
viewing Central Station Screen #1 so the display reads
Reporting Enabled
. Each
press of the
1
key will toggle the display between
Reporting Disabled
and
Reporting Enabled
.
RING COUNT
0-25 RANGE
Ring Count Screen
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=MANUAL DIAL MODE
On Board DACT Screen #2
CENTRAL STATION
1=REPORTING DISABLED
2=REPORT BACKUP
3=CALL LIMIT
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2