Programming the MS-9600 Fire Alarm Control Panel
Programming for DACT-UD
DACT-UD PN 51899:B1 1/25/05
17
SECTION 3
Programming for DACT-UD
3.1 Programming the MS-9600 Fire Alarm Control Panel
Refer to the MS-9600 Manual programming section for general programming
information. To program the MS-9600 FACP for use with the DACT-UD:
1. Press the
Enter
or
Mode
key to display the Read Status/Programming screen
2. Press
2
to access Programming
3. Enter the Master level password
4. Press the down arrow key twice to view the screen with the Option Modules
choice
5. Press
3
for Option Modules to access the Option Modules screen as shown to the
left
6. Program the FACP for use with the DACT-UD using the following procedure
3.1.1 On-Board DACT
The DACT-UD (Digital Alarm Communicator/Transmitter) is an optional module
which installs directly on the FACP main circuit board for communication to a
central station. Pressing
2
while viewing the Option Module Screen will cause the
following screens to be displayed:
3.1.1.1 DACT-UD Enable
To enable the on-board DACT module, press
1
while viewing On Board DACT
Screen #1 until the display reads
Enabled Yes
. The display will toggle between
Enabled Yes
and
Enabled No
with each press of the key.
OPTION MODULES
1=ANNUNCIATORS/UDACT
2=ON BOARD DACT
3=PRINTER/PC
Option Module Screen
ON BOARD DACT
1=ENABLED YES
2=PRIMARY PHONE
3=SECONDARY PHONE
On Board DACT Screen #1
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=MANUAL DIAL MODE
On Board DACT Screen #2