Installation in MS-9600 FACP
DACT-UD Installation
DACT-UD PN 51899:B1 1/25/05
15
3. Insert the supplied plastic snap-in standoff into mounting hole located at the
bottom center of the DACT-UD module (insert into back of board)
4. Carefully plug connector J1 on the back of the DACT-UD module into connector
J2 on the MS-9600 main circuit board, being careful not to bend any pins and at
the same time, insert plastic snap-in standoff into mounting hole in main board
5. Align the mounting holes in the DACT module with the premounted standoffs on
the FACP main circuit board
6. Secure the module to the standoffs on the main circuit board with the three
screws supplied with the DACT-UD. It is important that the supplied screws be
used to secure the module to the metal standoff in order to help protect against
electrical transients.
7. Reinstall the Keypad/Display on the main circuit board by positioning the unit
over the appropriate standoffs and securing with the screws which were loosened
in step 2
8. Make certain to program the control panel for DACT operation
Figure 2.3 DACT J1 Connector to FACP J2 Connector
J1
J2
Standoff
Standoff
Standoff (snap-in)
J1 Connector located on
back of DACT module
96dac
t2.C
DR
Standoff
Figure 2.4 DACT Installation on Standoffs
Mounting Screw
Mounting Screws
96dac
t3.CDR
Snap-in Standoff